FPA-1000-V2 Network Cards
this port. Recommended communication connection practice is to come out of one card and
in on the next. In cases where you are switching from a wired or fiber optic card to a different
type of card, you must use the Ethernet port which should be OUT not IN which is the default.
Move the jumper on this card so that Ground Fault Detection is disabled at this end of the
connection (making it an Ethernet OUT). Remove the jumper from both pins and replace it on
only one pin so that it does not get misplaced in case Ground Fault Detection needs to be re-
enabled later.
2.3

Port supervision

Each peer-to-peer connection to a networking card port used for panel-to-panel
communication must be supervised. This supervision is selected during programming.
For programming information, follow the panel programming instructions in the
FPA-1000Network Quick Installation Guide, or see Menu Structure (6‑PROGRAMMING,
8‑NETWORKING) or Overview of the web user interface (Networking) in the FPA-1000
Installation and Operation Guide.
Bosch Security Systems, Inc.
Installation manual
Planning information | en
2017.11 | 2.0 | F.01U.214.374
7