Siemens SIMATIC S5 Manual page 67

Interface of the programmable controller
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

S5-95U, SINEC L2
3.4.3
Assigning Parameters in DB1 for the FMA Services
The default settings of DB1 do not enable the FMA services. To activate the FMA services, set the
following parameters in DB1:
The job number A-NR=200 (200 is reserved for FMA services)
The location of a status byte (STB) for FB L2-SEND and FB L2-RECEIVE.
The status byte displays the status of the transmit or receive jobs and informs you of possible
errors. Section 5.4 explains in detail the structure and the evaluation of the STB. The STB
parameter settings provide you with access to all the FMA services described in section 3.6.2,
except MAC_EVENT. If you want to use MAC_EVENT, you must specifically activate this service
in DB1.
Figure 3-9 shows DB1 with parameter settings for all FMA services.
The procedures to set and modify parameters in DB1 and to transfer DB1 are described in detail in
section 1.4.
156:
KS
='
168:
KS
=' BDR 500
180:
KS
='5120
192:
KS
='SDT 1 12
204:
KS
='STB 200
.
.
.
Figure 3-9. DB1 with Parameter Settings for All FMA Services
Table 3-4 shows the parameters to use for FMA services.
Parameter
Blockkennung: SL2:
STB
FMAE
Argument
200 MBx
J/Y/N
EWA 4NEB 812 6112-02
SL2: TLN 1
STA AKT';
HSA 10
TRT ';
SET 0
ST 400
';
SDT 2 360
';
MB200 FMAE Y
';
Table 3-4. DB1 Parameters for the FMA Services
Argument
200 MBx
J/Y/N
Permissible Range
1 ... 253
Start-Up, Tests, and Diagnostics
Significance
SINEC L2
Location of status byte for FMA services
Job number A-NR=200
Activate FMA service MAC_EVENT
Explanation
Job number, flag byte
Is FMA service activated?
j/J = ja; y/Y = yes; n/N = nein
3-13