6 TROUBLESHOOTING
6 TROUBLESHOOTING
The details of the errors which may occur when using the AJ65VBTCU-68ADVN/ADIN
and troubleshooting are described.

6.1 Error Code List

If an error occurs (the "RUN" LED of the AJ65VBTCU-68ADVN/ADIN flickers) during
write of data from the PLC CPU to the master module, the corresponding error code is
stored into the remote register RWrn+8 of the AJ65VBTCU-68ADVN/ADIN.
(1) If the average time/number of times setting error occurs, the "RUN" LED flickers at
(2) If two or more errors occurred, the error code of the first error is stored and the
(3) To reset the error code, turn on the error reset request flag RY(n+1)A.
6 - 1
Table 6.1 Error Code List (Errors detected by AJ65VBTCU-68ADVN/ADIN)
Error Code
(Decimal)
The average number of times setting is
10
outside the range.
The average time setting is outside the
11
range.
The input range setting is outside the
20
setting range.
intervals of 0.5s and A/D conversion processing is performed with the average
time or number of times used prior to error occurrence.
If the input range setting error occurs, the "RUN" LED flickers at intervals of 0.1s
and A/D conversion processing is not performed on all channels
other errors are not stored.
Cause
Correct the average number of
times setting to within 1 to 10000.
Correct the average time setting
to within 4 to 10000.
Correct the input range setting to
within the setting range.
indicates the channel No. where the error occurred.
MELSEC-A
Action
6
.
6 - 1