1MRS755382
Station Automation COM600 3.4
IEC 60870-5-101 Slave (OPC) User's Manual
Property / Para-
Value or Value range/ Default
meter
Receiver Data Bit
5...8
Count
Default: 8
Stop Bits
1 stopbit
2 stopbits
Default: 1 stopbit
Transmitter Data Bit
5...8
Count
Default: 8
Communication
Control
Carrier Blocking
Carrier detect signal is ignored
Carrier detect signal must be
set
Default: Carrier detect signal
must be set
CTS Delay
0...65535
Default: 50
Enquiry Limit
0...255
Default: 3
Header Timeout
0...65535
Default: 2000
Keep Alive Timeout
0...65535
Default: 5000
Link Type
RTS activated during transmis-
sion (Unbalanced slave)
RTS always active, reception
always enabled (Balanced
slave)
RTS activated during transmis-
sion, reception always enabled
(Balanced slave)
Default: RTS always active,
reception always enabled (Bal-
anced slave)
Description
Specifies the number of data bits in each
received character.
Specifies the number of data bits in each
transmitted character.
Specifies the number of stop bits attached
to each transmitted character.
Determines whether the Carrier Detect
signal of the serial port must be set in
order for the IEC station to receive mes-
sages
Delay in milliseconds between activation
of the RTS signal and start of new trans-
mission.
Specifies maximum number of times that
a message is transmitted after timeout.
Maximum waiting time in milliseconds of
a link layer response.
The connection is considered to be alive
if the delay between two consecutive
master messages is shorter than the spe-
cified time in milliseconds.
The type of the data link connection used
on the channel.
23