5.4 SYSTEM SETUP
PMU AGGREGATOR1 PROTOCOL: This setting selects if C37.118 or the new IEC61850 standard will be used. In
firmware release 6.0 only C37.118 will be available.
PMU AGGREGATOR1: TCP PORT: This setting selects the TCP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
PMU AGGREGATOR1 UDP PORT: This setting selects the UDP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
PMU AGGREGATOR1 PDC CONTROL: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in table 2. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is re-started. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
Table 5–11: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
5
as above
as above
as above
as above
as above
PMU AGGREGATOR1 PMU1 to PMU4: If set to Yes aggregator 1 will include PMU1 data set in the reporting data
stream. Aggregator 1 will not include PMU1 data set in the report if set to No. For a system frequency of 60Hz (50 Hz)
the UR will generate a Reporting Mismatch message if the selected rate isn't 10Hz, 12Hz, 15Hz, 20Hz, 30Hz, 60 Hz,
120 Hz (10Hz, 25Hz, 50Hz or 100Hz) when entered via the keypad or software and the UR will stop the transmission
of reports. Note: If changes are made to PMU settings the PMU must be removed from the aggregator and the settings
saved and then the PMU should be added back into the aggregator and the settings saved such that the new PMU set-
tings take effect.
5-92
OPERAND SYNTAX
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
L30 Line Current Differential System
OPERAND DESCRIPTION
Phasor data concentrator asserts control bit 1, as
received via the network.
Phasor data concentrator asserts control bit 2 as
received via the network.
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.
5 SETTINGS