External Power Supply Circuit; Figure 25: Connecting Wires To The Wago Connector Block - ABB FOX615 Installation & User Manual

Table of Contents

Advertisement

3.4.2.2

External power supply circuit

WARNING
External power supply circuit
connection
FOX615
Installation
4. Snap the studs of the block into the 2 holes from inside the cable tray,
while the cable tail is looking to the rear of the cable tray.
5. Check the WAGO connector block for firm fit.
6. Repeat steps 1 ... 5 if you want to install a second power cable on the
opposite side of the cable tray for dual power source supply.
End of instruction
Hazardous electric currents. Risk of flashover and electric shock!
Make sure that
→ The external - 48/60 V
power leads to the WAGO connector block(s).
→ The power cables provide sufficient insulation (e.g. near the WAGO
connector block).
With life power supplies short circuits with flash over might result.
2

Figure 25: Connecting wires to the WAGO connector block

Legend to symbols of connector block:
+
0 Volt conductor for power supply (red wires)
-
- 48/60 Volt DC for power supply (blue wires)
Proceed as follows:
1. Arrange the 2 wires (max. 4 mm
ply and the 2 wires (max. 4 mm
connector block installed on the cable tray.
2. Select the first wire of the power return (+).
I N S T A L L A T I O N P R O C E D U R E S
power is switched off before you connect the
DC
3
1
2
) with the negative voltage power sup-
2
) of the power return close to the WAGO
10 - 11 mm
45