ETHERNET INTERFACE

IEC 61850 GOOSE communications

EnerVista SR3 Setup
software structure
1–62
The 345 firmware supports IEC61850 GOOSE communications on the optional
communications daughter board.
Portions of the IEC61850 standard not pertaining to GOOSE, are not implemented in the
345 relay.
The 345 relay does not support
an IEC61850 MMS server
the mapping of analogue values to data points in data sets in either the transmit or
receive direction
a file system to maintain SCL, ICD or CID files, for IEC61850 GOOSE. As such the
implementation stores GOOSE configuration using MODBUS set points.
Configuration of transmission and reception settings for the GOOSE feature are performed
using EnerVista SR3 Setup Software.
The 345 firmware accepts GOOSE messages from UR, F650 and UR Plus. The
interoperability with other manufacturers will be guaranteed in almost all cases, by
implementing the reception side with nested structures (one level of nesting) and all the
standard data types.
GOOSE settings changes will take effect only after the 345 relay is re-booted. One setting is
available to Enable/Disable both Transmission and Reception. It is possible to change this
setting from the Front Panel of the relay.
Figure 1: EnerVista SR3 GOOSE General Settings
The structure below reflects how the EnerVista SR3 Setup software should be used to
implement the sections detailed in this document, in order to enable both transmission
and reception of GOOSE messages.
CHAPTER 1: COMMUNICATIONS GUIDE
345 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE