2-4. Choosing the outdoor unit installation location

OK
OK

2-5. Minimum installation area

If you unavoidably install a unit in a space where all four sides are blocked or there are depressions, confirm that one of
these situations (A, B or C) is satisfied.
Note: These countermeasures are for keeping safety not for specification guarantee.
A) Secure sufficient installation space (minimum installation area Amin).
Install in a space with an installation area of Amin or more, corresponding to refrigerant quantity M (factory-charged
refrigerant + locally added refrigerant).
M [kg]
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
B) Install in a space with a depression height of [ 0.125 [m]
Height from the bottom of
0.125 [m] or less
OCH653
OK
NG
Amin [m²]
12
17
23
28
34
39
45
50
56
62
67
73
78
84
R32 is heavier than air—as well as other refrigerants—
so tends to accumulate at the base (in the vicinity of the
floor). If R32 accumulates around base, it may reach a
flammable concentration in case room is small. To avoid
ignition, maintaining a safe work environment is required
by ensuring appropriate ventilation. If a refrigerant leak is
confirmed in a room or an area where there is insufficient
ventilation, refrain from using of flames until the work
environment can be improved by ensuring appropriate
ventilation.
Install outdoor units in a place where at least one of the
four sides is open, and in a sufficiently large space with-
out depressions.
Amin
Height from the bottom of
0.125 [m] or less
10