Standard Connection Diagram - Toshiba Tosvert VF-S15 Instruction Manual

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

2.2.2

Standard connection diagram 2

Standard connection diagram - SOURCE (Positive) (common:P24)
Main circuit power supply
3ph-200V class: three-phase 200-240V
-50/60Hz
1ph-200V class: single-phase 200-240V
-50/60Hz
3ph-400V class: three-phase 380-500V
-50/60Hz
MCCB(2P)
Single
R/L1
phase
Power
S/L2/N
supply
Protective function
*1: The T/L3 terminal is not provided for
single-phase models.
Use the R/L1 and S/L2/N terminals as
input terminals.
*2: The inverter is supplied with the PO
and the PA/+ terminals shorted by
means of a shorting bar.
Before installing the DC reactor (DCL),
remove the bar.
*3: When using the NO output terminal in
source logic mode, short the P24 and
OUT terminals.
*4: When VIA or VIB terminal is used as logic
input terminal, refer to section 7.2.1.
*5: To supply control power from an external
power supply for backing up the control
power supplied from the inverter, an optional
control power backup device (CPS002Z) is
required. In such a case, the backup device
is used at the same time with the internal
power supply of the inverter.
The optional control power backup unit can
be used with both 200V and 400V models.
*6: Set the slide switch SW1 to source side.
Refer to page B-11,12 for details.
Default setting is SINK side.
*7: When STO terminal is used as compliance
with safety functions, refer to Safety
function manual (E6581860).
DC reactor (DCL)
*2 (option)
P0
*1
MCCB
R/L1
S/L2
Noise
filter
T/L3
STO
*7
+SU
Control power
supply
CC
*5
VF-S15
FLA
FLB
activation output
FLC
RY
SINK
Low-speed
signal output
RC
VIB
PTC
FM
CC
VIC
+
Meter
Frequency
meter
(ammeter)
-
1mA
(or 4-20mA/0-10V)
External potentiometer (1k-10kΩ)
(or voltage signal between VIA and CC: 0-10V)
B-5
Braking resistor(Option)
PA/+
PB
PC/-
U/T1
V/T2
Power circuit
W/T3
F
Control
circuit
R
RES
S1
S2
S3
Operation panel
P24
*6
SW1
*3
OUT
SOURCE
NO
PLC
RS485
CC
SW2
connector
S4
S3
*4
*4
VIB
VIA
PP
E6581926
Motor
M
Forward run command
Reverse run command
Reset
Preset-speed command 1
Preset-speed command 2
Preset-speed command 3
Common
Ry
Speed reach
signal output
Current signal: 4(0)-20mA
Voltage signal: 0-+10V
(or -10-+10V)
2