8. TROUBLESHOOTING
8.2.2

Errors caused by incorrect parameter settings or abnormal network

RUN
L.RUN
MS
LED
LED
LED
LED
l
O
l
¥
l
¥ r
Green
l
¥
Green
l
l
l
NS
Status
Communication stopped
Communication ready
Parameter error
Parameter error
Red
Timeout occurred at a
¥
connection.
Check item
Are parameters set?
Wait and see
Check the parameters.
Check the parameters.
Wrong connection type for a
slave station?
Is the slave station power
turned ON?
Is the same baud rate set for all
slave stations?
Is a termination resistance
connected?
Is the communication cable
correctly connected?
Does the total cable length
exceed the permitted limit?
Does the drop line length or
total drop line length exceed the
permitted limit?
Is the network power supply
correctly connected?
Is the network power supply
capacity sufficient?
Is the production inhibit time set
too short in the parameters?
Is the expected packet rate set
too short in the parameters?
Incorrect slave I/O data length
in the parameters?
l : Lit O : Not lit ¥: Flashing ¥ r: Flashing (random)  : Undetermined
8
6
MELSEC-A
Remedy
Set parameters.
Parameters are defective if
flashing continues. Repair or
replace the parameters.
Correct the parameters.
Correct the parameters.
Correct the parameters.
Turn ON the slave station power.
Set the same baud rate for all
slave stations.
Connect a termination
resistance.
Correctly connect the
communication cable.
Reduce the baud rate.
Reduce the total cable length.
Reduce the baud rate.
Reduce the drop line length or
total drop line length.
Correctly connect the network
power supply.
Increase the network power
supply capacity.
Change the position of the
network power supply.
Correct the parameters.