Ordering; Order Codes; Specifications; Mechanical - GE D485 Instruction Manual

Modbus to devicenet
Table of Contents

Advertisement

INTRODUCTION

ORDER CODES

MECHANICAL

ELECTRICAL
CHARACTERISTICS

COMMUNICATIONS

ENVIRONMENTAL

EMC COMPLIANCE

1–4

Ordering

The following table illustrates the order codes for the D485 Modbus to DeviceNet
Converter.
Table 1–1: D485 order codes
D485
– *
Base unit
D485
|
C
X

Specifications

HOUSING
Plastic housing with snap-on connection to DIN-rail, protection class IP20
DIMENSIONS
L x W x H:
120 mm × 75 mm × 27 mm
(4.72-in × 2.95-in × 1.06-in)
PROTECTION CLASS
Protection class:
IP20
POWER SUPPLY
Power:
24 V ±10% (for use in class 2 circuits)
POWER CONSUMPTION
Maximum power consumption: 280 mA on 24 V
Typically power consumption: approximately 100 mA
BAUD RATES
Baud rate (DeviceNet)
125, 250, and 500 kbps
Baud rate (Modbus)
1200, 2400, 4800, 9600, 19200, 38400, and 57600 bps
I/O DATA
I/O input size:
512 bytes
I/O output size:
512 bytes
FEATURES AND INTERFACE
Supported features:
bit strobe, polling, cyclic and COS I/O messaging, explicit messaging
Modbus interface:
RS232, RS422, RS485
DeviceNet interface:
5-pin linear DeviceNet plug (Phoenix type)
RELATIVE HUMIDITY
The product is designed for a relative humidity of 0 to 95% non-condensing
TEMPERATURE
Operating:
0 to 55°C
Non Operating:
–5 to 85°C
CE-MARK
Certified according to European standards unless otherwise is stated
Emission:
according to EN 50081-2:1993
Immunity:
according to EN 61000-6-2:1999
UL/C-UL COMPLIANCE
This unit is an open type listed by the Underwriters Laboratories.
The certification has been documented by UL in file E214107.
D485 Modbus to DeviceNet Converter
With configuration cable
No configuration cable
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE

Advertisement

Table of Contents
loading

Table of Contents