If there is no second busbar B at the other side of the transformer and therefore no
QB4 disconnector, then the state for QB4 is set to open by setting the appropriate
module inputs as follows:
QB4_OP = 1
QB4_CL = 0

Interlocking for bus-section breaker A1A2_BS

Application
The interlocking for bus-section breaker (A1A2_BS) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure 142. The
function can be used for different busbars, which includes a bus-section circuit
breaker.
WA1 (A1)
QC1
IEC04000516 V1 EN-US
Figure 142:
Switchyard layout A1A2_BS
The signals from other bays connected to the module A1A2_BS are described
below.
Signals from all feeders
If the busbar is divided by bus-section circuit breakers into bus-sections and both
circuit breakers are closed, the opening of the circuit breaker must be blocked if a
bus-coupler connection exists between busbars on one bus-section side and if on
the other bus-section side a busbar transfer is in progress:
WA2 (A2)
QB1
QB2
QA1
QC3
QC4
A1A2_BS
Section 14
Control
QC2
en04000516.vsd
IP14154-1 v2
M15110-3 v7
M15111-4 v3
M15111-6 v4