Setting Guidelines - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 8
Current protection
8.13.3
222
may cause cavitations. The risk for damages to hydro turbines can justify reverse
power protection in unattended plants.
A hydro turbine that rotates in water with closed wicket gates will draw electric power
from the rest of the power system. This power will be about 10% of the rated power. If
there is only air in the hydro turbine, the power demand will fall to about 3%.
Diesel engines should have reverse power protection. The generator will take about
15% of its rated power or more from the system. A stiff engine may require perhaps
25% of the rated power to motor it. An engine that is well run in might need no more
than 5%. It is necessary to obtain information from the engine manufacturer and to
measure the reverse power during commissioning.
Gas turbines usually do not require reverse power protection.
Figure
89
illustrates the reverse power protection with underpower IED and with
overpower IED. The underpower IED gives a higher margin and should provide better
dependability. On the other hand, the risk for unwanted operation immediately after
synchronization may be higher. One should set the underpower IED to trip if the active
power from the generator is less than about 2%. One should set the overpower IED to
trip if the power flow from the network to the generator is higher than 1%.
Underpower IED
Q
Operate
Line
Margin
P
Operating point
without
turbine torque
IEC06000315 V2 EN-US
Figure 89:
Reverse power protection with underpower IED and overpower IED

Setting guidelines

GlobalBaseSel: Selects the global base value group used by the function to define
IBase, VBase and SBase as applicable.
Operation: With the parameter Operation the function can be set Enabled/Disabled.
Overpower IED
Q
Operate
Line
Margin
Operating point
without
turbine torque
IEC06000315-2-en.vsd
1MRK 511 401-UUS A
P
Bay control REC670 2.2 ANSI
Application manual
SEMOD172150-4 v7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents