Chapter 2
Installing the Device
•
Section 2.6, "Grounding the Device"
•
Section 2.7, "Connecting the Failsafe Alarm Relay"
•
Section 2.8, "Connecting Power"
•
Section 2.9, "Connecting to the Device"
•
Section 2.10, "Configuring the Device"
Section 2.1
General Procedure
The general procedure for installing the device is as follows:
1.
Review the relevant certification information for any regulatory requirements. For more information, refer to
Section 6.1,
"Approvals".
2.
Review the RUGGEDCOM RX5000 Modules Catalog for special installation or regulatory requirements related
to the modules installed in the device.
3.
Mount the device.
4.
Connect the failsafe alarm relay.
5.
Connect power to the device and ground the device to safety Earth.
6.
Connect the device to the network.
7.
Configure the device.
Section 2.2
Required Tools and Materials
The following tools and materials are required to install the RUGGEDCOM RX5000:
AC or DC power cord (16 AWG)
CAT-5 Ethernet cables
Phillips screwdriver
4 x #8-32 screws
Section 2.3
Cabling Recommendations
Before connecting the device, be aware of the recommendations and considerations outlined in this section.
CONTENTS
•
Section 2.3.1, "Protection On Twisted-Pair Data Ports"
6
Tools/Materials
For connecting power to the device.
For connecting the device to the network.
For mounting the device to a panel.
For mounting the device to a panel.
RUGGEDCOM RX5000
Installation Guide
Purpose
General Procedure