Parameters/address space
4.1 Parameters
Parameter
Input delay
Potential group
Only when configuring using a PROFIBUS GSD file; does not apply to configuration with STEP 7 via HSP. The parame-
1
ter assignment options are limited because PROFIBUS GSD configuration limits the number of parameters to a maxi-
mum of 244 bytes for each ET 200SP station. If required, you can still assign these parameters using the data record
128 as described in the column "GSD file PROFINET IO" (see table above). The parameter length of the I/O module is
16 bytes.
18
Value range
None
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
Use potential group of
the left module (mod-
ule plugged into a
dark-colored BaseUnit)
Enable new potential
group (module plugged
into light-colored Ba-
seUnit)
Default
Reconfig-
uration in
RUN
3.2 ms
Yes
Use potential
No
group of the left
module
Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0)
Scope with configuration software,
e.g. STEP 7 (TIA Portal)
GSD file
GSD file
PROFINET IO
PROFIBUS DP
Channel
Module
Module
Module
Manual, 09/2017, A5E32855511-AC