SYSTEM SETUP
IEC 61850–90–5 PMU 1 configuration
SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT BASIC CONFIGURATION PMU 1 PMU 1 BASIC
CONFIGURATION 90-5 PMU 1 CONFIGURATION
90-5 PMU 1
CONFIGURATION
— A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
PMU1 LDINST
logical device.
As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64
characters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.
5.5.8.10 PMU calibration
SETTINGS SYSTEM SETUP PHASOR MEASUREMENT UNIT PHASOR MEASUREMENT UNIT 1 PMU 1
CALIBRATION
PMU 1
CALIBRATION
5
5-174
PMU 1 LDINST:
PMU1
PMU 1 VA CALIBRATION
°
ANGLE: 0.00
PMU 1 VA CALIBRATION
MAG: 100.0%
PMU 1 VB CALIBRATION
ANGLE: 0.00°
PMU 1 VB CALIBRATION
MAG: 100.0%
PMU 1 VC CALIBRATION
ANGLE: 0.00°
PMU 1 VC CALIBRATION
MAG: 100.0%
PMU 1 VX CALIBRATION
ANGLE: 0.00°
PMU 1 VX CALIBRATION
MAG: 100.0%
PMU 1 IA CALIBRATION
ANGLE: 0.00°
PMU 1 IA CALIBRATION
MAG: 100.0%
PMU 1 IB CALIBRATION
ANGLE: 0.00°
PMU 1 IB CALIBRATION
MAG: 100.0%
PMU 1 IC CALIBRATION
ANGLE: 0.00°
PMU 1 IC CALIBRATION
MAG: 100.0%
PMU 1 IG CALIBRATION
ANGLE: 0.00°
PMU 1 IG CALIBRATION
MAG: 100.0%
Range:
64 char ASCII text
Range:
–5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS