Section 4
Binary input and output modules
4.1.3
4.1.3.1
Table 8:
BIO_9BI Non group settings (basic)
Name
Values (Range)
BatteryVoltage
24 - 250
Table 9:
BIO_9BI Non group settings (advanced)
Name
Values (Range)
Threshold1
6 - 900
DebounceTime1
0.000 - 0.100
OscillationCount1
0 - 255
OscillationTime1
0.000 - 600.000
Threshold2
6 - 900
DebounceTime2
0.000 - 0.100
OscillationCount2
0 - 255
OscillationTime2
0.000 - 600.000
Threshold3
6 - 900
DebounceTime3
0.000 - 0.100
OscillationCount3
0 - 255
OscillationTime3
0.000 - 600.000
Threshold4
6 - 900
DebounceTime4
0.000 - 0.100
OscillationCount4
0 - 255
OscillationTime4
0.000 - 600.000
Threshold5
6 - 900
DebounceTime5
0.000 - 0.100
OscillationCount5
0 - 255
OscillationTime5
0.000 - 600.000
Table continues on next page
58
Each binary input has an oscillation count parameter OscillationCountx and an oscillation
time parameter OscillationTimex, where x is the number of the binary input of the module
in question.

Settings

Setting parameters for binary input modules

Unit
Step
V
1
Unit
Step
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001
%VB
1
s
0.001
-
1
s
0.001
Default
Description
110
Station battery voltage
Default
Description
65
Threshold in percentage of station battery
voltage for input 1
0.005
Debounce time for input 1
0
Oscillation count for input 1
0.000
Oscillation time for input 1
65
Threshold in percentage of station battery
voltage for input 2
0.005
Debounce time for input 2
0
Oscillation count for input 2
0.000
Oscillation time for input 2
65
Threshold in percentage of station battery
voltage for input 3
0.005
Debounce time for input 3
0
Oscillation count for input 3
0.000
Oscillation time for input 3
65
Threshold in percentage of station battery
voltage for input 4
0.005
Debounce time for input 4
0
Oscillation count for input 4
0.000
Oscillation time for input 4
65
Threshold in percentage of station battery
voltage for input 5
0.005
Debounce time for input 5
0
Oscillation count for input 5
0.000
Oscillation time for input 5
1MRK 502 048-UUS A