Issue 08/03
Parameter
Parameter Description
Number
P0309[0]
Enter Rated Motor Efficiency
(enter value from motor name plate)
If the setting is 0, the value is automatically calculated.
NOTE
You will not see this parameter in your BOP or AOP if
P0100=0.
Always enter the value from the motor name plate if you
have it. If this figure is calculated too low then you may
trip on F0041 (Motor ID Failure) or F0011 (Motor
Overtemperature).
P0310[0]
Enter Rated Motor Frequency
(enter value from motor name plate)
NOTE
Typically this will already have been set by the DIP2(2)
switch, however if you have a non-standard motor, here
is where you enter the nominal frequency.
The number of pole pairs is automatically calculated
P0311[0]
Enter Rated Motor Speed
(enter value from motor name plate)
If the setting is 0, the value is internally calculated.
NOTE
An entry must be made for closed-loop Vector control,
V/f control with FCC and for slip compensation.
P0320[0]
Enter Motor Magnetization Current
(enter value from motor name plate or data sheet)
If setting is 0, the value is internally calculated.
P0335[0]
Enter Motor Cooling Method*
0
1
P0500[0]
Enter Technological Application
0
1
3
NOTE
See P0205
48
Self-cooled using shaft mounted fan attached to
the motor
Force-cooled: Using a separately powered cooling
fan
Constant Torque
Pumps and Fans
Simple Positioning
Quick Start Guide
Suggested
User
Setting
Setting
From
Name
Plate
From
Name
Plate
From
Name
Plate
0
0
0
MICROMASTER 440