6.6 Attaching Surge Suppressor for Control Equipment

If an improper operation such as communication error occurs in the
GOT in synchronization with ON/OFF of a particular control equipment
(hereinafter abbreviated to load) such as MCCB, electromagnetic
contactor, relay, solenoid valve, or induction motor, the GOT may be
influenced by surge noise.
In such a case, install the ground cable or communication cable apart
from the load.
If the ground cable or communication cable has to be installed close to
the load unavoidably, attaching a surge suppressor is effective.
Attach the surge suppressor at the position closest to the load.
Output equipment
such as PLC's
output module
Output equipment
such as PLC's
output module
The GOT's ground cable and communication cable
must not be installed close to the load.
Output
AC
Measures for AC inductive load
The GOT's ground cable and communication cable
must not be installed close to the load.
Output
DC
Measures for DC inductive load
52
C
L Load
R
The surge suppressor must
be attached close to the load.
D
L Load
The surge suppressor must
be attached close to the load.