ABB i-bus KNX Product Manual page 21

Fan coil/systemised building technology
Hide thumbs Also See for i-bus KNX:

Advertisement

Designation
Send the heating/cooling
control value
cycl. sending of the
heating/cooling control
value
Proportional range of the
heating control unit
Integration time of the
heating controller
Values
with a change of 1 %
with a change of 2 %
with a change of 3 %
with a change of 5 %
with a change of 7 %
with a change of 10 %
with a change of 15 %
not cyclical, only with a
change
every 2 mins., every 3
mins.
every 5 mins., every 10
mins.
every 15 mins., every 20
mins.
every 30 mins., every 45
mins.
every 60 mins.,
User-defined control parameters
1 K, 1.5 K, 2 K, 2.5 K, 3 K
3.5 K, 4 K, 4.5 K
5 K, 5.5 K, 6 K
6.5 K, 7 K, 7.5 K
8 K, 8.5 K
15 mins., 30 mins., 45
mins.
60 mins., 75 mins., 90
mins.
105 mins., 120 mins., 135
mins.
150 mins., 165 mins., 180
mins.
195 mins., 210 mins., 225
mins.
Meaning
After what % change** in
the control value is the new
value to be sent?
Small values increase the
control accuracy, but also
the bus load.
how often does the current
heating control value need
to be sent (regardless of
changes)?
Professional setting for
modifying the control
behaviour for the room.
Small values result in large
changes in the control
values; larger values result
in a less dramatic change
in the control value.
See in appendix:
T emperature control
H U
The integration time
determines the response
time of the controller.
It specifies the increase by
which the output control
value is increased in
addition to the P-
component. The I-
component remains active
for as long as there is a
control deviation. The I-
component is increased by
the P-component.
See in appendix:
B ehaviour of the PI
H U
controller
U H
U H
21