Measurement Verification (P709 To P713) - Siemens sitrans PROBE LU Instruction Manual

2-wire loop powered ultrasonic transmitter for level, volume and flow monitoring of liquids
Hide thumbs Also See for sitrans PROBE LU:
Table of Contents

Advertisement

Enter a value slightly greater than the vessel's maximum emptying rate, in Units (P005) or
percent of Span (P007) per minute.
P003 Value
1
2
3

Measurement Verification (P709 to P713)

P709 Damping Filter
Stabilizes the reported level within the Echo Lock Window (P713) in the event of level
fluctuations (for example, a rippling or splashing liquid surface). The value is in seconds,
and depends on the number of seconds it takes the device to reach 63% of a step value
change in reading.
Values
Altered by
Related
The value is automatically altered when Measurement Response Speed (P003) changes.
The higher the value entered, the greater the range of stabilized fluctuation.
P711 Echo Lock
Use this feature to select the measurement verification process.
Values
Related
Page 50
SITRANS Probe LU – INSTRUCTION MANUAL
Meters/Minute
0.100
1.0000
10.000
Range
Default
P003 Measurement Response
P007 Span
P713 Echo Lock Window
0
Off
1
Maximum Verification
2
*
Material Agitator
3
Total Lock
P700 Maximum Fill Rate
P701 Maximum Empty Rate
P712 Echo Lock Sampling
P713 Echo Lock Window
P820 Algorithm
0 to 100.00 seconds (0 = off)
10.000 seconds
7ML19985HT01