Step 2.
Connect the MBP detection cable
Step 3.
Slide the MBP I/O cover
Step 4.
Insert the Normal AC source cable through the cable gland.
Step 5.
Connect the wires to the Normal AC source (Input) terminal blocks (do not remove the Input Bypass
AC jumper
Step 6.
Insert the Output cable through the cable gland.
Step 7.
Connect the wires to the Output terminal blocks.
Step 8.
Tighten the cable glands.
Step 9.
Slide back and secure the MBP I/O cover
8/11k VA 3Phase with separate Normal and Bypass AC source
Step 1.
Slide the MBP Bypass Input cover
Step 2.
Punch the UPS Bypass Input knockout of the MBP Bypass Input cover
cable gland inside.
34
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
after removing the 5 screws, to access to MBP terminal blocks.
and the UPS Input Bypass jumper inside the UPS I/O cover.
to the specific UPS connector.
with the 5 screws.
after removing the 3 screws.
and insert a provided