Siemens SINAMICS G120P Operating Instructions Manual page 13

Filter for pm330 power module
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

Risk of destruction during operation with increased pulse frequency
When a du/dt filter compact plus Voltage Peak Limiter is used with SINAMICS G120, the
pulse frequency of the Power Module must not exceed 2.5 kHz or 4 kHz. Setting a higher
pulse frequency can lead to destruction of the du/dt filter.
Note
Current derating at increased pulse frequency
Current derating at an increased pulse frequency depends on the derating of the associated
Power Module.
NOTICE
Activation during commissioning
If a du/dt filter compact plus Voltage Peak Limiter is connected to the Power Module, it is
essential that it is activated during commissioning (p0230 = 2).
Table 2- 2
Max. pulse frequency when a du/dt filter compact plus Voltage Peak Limiter is used in units with a rated pulse
frequency of 2 kHz
Order no. of the
Rated power
Power Module
6SL3310-...
1PE33-0AA0
1PE33-7AA0
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 11/2013, A5E32847614B AA
WARNING
Output current for a
[kW]
pulse frequency of 2 kHz [A]
Line voltage 380 V – 480 V 3 AC
160
200
compact plus Voltage Peak Limiter is used
300
370
Max. pulse frequency when a du/dt filter
4 kHz
4 kHz
General
13

Advertisement

Table of Contents
loading

Table of Contents