[Installation precautions]
When
When the wall mounting type is installed in a
installation
bedroom, living room, or other quiet place, the
environment is
sound o the re rigerant ow
quiet
as noise and must be taken into accunt.
When
In the case of the ceiling chamber system
installing duct
(duct is not installed at indoor unit inlet
type in ceiling
side and room air is sucked into the indoor
chamber
unit through the inside of the ceiling), the
system
thermistor inside the indoor unit may not
correctly detect the room temperature.
Heating operation: Room is not heated
because the indoor unit is easily turned off by
the thermostat.
Cooling operation: Room is too cold because
the indoor unit is di ficu t to turn o b the
thermostat.
When the
Cooling operation does not cool the room
outlet air is
and heating operation does not heat the room
sucked in at
because the short circuited indoor unit is not
duct type
turned on by the thermostat.
When using
Signals may not be received when using it in
the wireless
a roo
remote
lamp.
controller
When
It may generate noise in TV sets, stereos and
installing the
PCs.
inverter type
Contents
a be sensed
i u inated b an in erter uorescent
- (06 - 153) -
Countermeasures (Reference)
1) Plan installation of a model
with external expansion
valve.
2) Plan installation of a branch
box farther from indoor
unit.
3) Plan installation using
another air conditioner.
1) Replace the indoor unit
thermistor with a Remote
sensor unit (optional
parts) and install the
sensor where the room
temperature can be
correctly detected
1) Reconsider the ventilation
port construction
2) Replace the indoor unit
thermistor with a Remote
sensor unit (optional
parts) and install the
sensor where the room
temperature can be
correctly detected.
urn on the uorescent
lamp and check if the
indoor unit receives the
signals from the remote
controller.
If the indoor unit does
notreceive the signals,
consult an authorized
service personnel.
1) The inverter type should
be insta ed at a su ficient
distance from these
equipments.
6. SYSTEM DESIGN