Toshiba TOSVERT VF-AS3 Instruction Manual page 149

Industrial inverter (for 3-phase motors)
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

The output frequency changes to the frequency
command value set with <Sr1: Preset speed 1>
and becomes stable.
In the example on the right, it is 20.0 Hz.
The following are always displayed in the status
area on the upper side of the screen regardless of
display mode. (From the left)
• The
icon is rotating
• Operation status "RUN"
• Output frequency (display contents vary
depending on the setting of the parameter)
• Run command icon
18 When you turn on relay 2 with relay 1 on, the
frequency command value of <Sr3> is enabled,
and the output frequency changes.
The output frequency changes to the frequency
command value set with <Sr3: Preset speed 3>
and becomes stable.
In the example on the right, it is 15.0 Hz.
19 When you turn off relay 1 with relay 2 on, the
frequency command value of <Sr2> is enabled,
and the output frequency changes.
The output frequency changes to the frequency
command value set with <Sr2: Preset speed 2>
and becomes stable.
In the example on the right, it is 10.0 Hz.
20 When you turn off the external switch, the motor
decelerates and stops.
Memo
• For details of preset speed operation, refer to [5. 2. 7].
Easy
Output frequency
0
[F]-[CC]
[S1]-[CC]
[S2]-[CC]
Easy
Easy
4-41
4. [Basic operation] Operation methods of motor
E6582062
RUN
20.0Hz
20:51
Standard Mode
20.0
Hz
Screen
Copy
Monitor
<Sr1>
<Sr3>
<Sr2>
Time
ON
OFF
ON
OFF
ON
OFF
RUN
15.0Hz
16:04
Standard Mode
15.0
Hz
Screen
Copy
Monitor
RUN
10.0Hz
16:05
Standard Mode
10.0
Hz
Screen
Copy
Monitor
3
4
9