ABB i-bus KNX Product Manual page 33

Knx/enocean gateway
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®

i-bus
KNX
On/Off
Status_ On/Off
Status_ Mode
Status_ Mode Auto
Status_ Mode Heat
Mode
Status_ Mode Cool
Status_ Mode Fan
Status_ Mode Dry
Status_ Fan Speed / 14 Speeds
Status_ Fan Speed / 14 Speeds
Status_ Fan Speed Manual/Auto
Status_ Fan Speed 1
Fan Speed
Status_ Fan Speed 2
Status_ Fan Speed 3
Status_ Fan Speed 4
Status_ Fan Speed 5
Status_ Vane Position
Status_ Vane Position / 5 Positions
Status_Vane Manual/Auto
Vanes
Status_ Vane Position 1
Status_ Vane Position 2
Status_ Vane Position 3
ABB STOTZ-KONTAKT GmbH
Eppelheimer Straße 82, 69123 Heidelberg, Germany
 +49 (0) 6221 701 607
 +49 (0) 6221 701 724
EG/A 32.2.1
1 bit
DPT_Switch
1.001
1 byte
DPT_HVACContrMode
20.105
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 byte
DPT_Scaling
5.001
1 byte
DPT_Enumerated
5.010
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 byte
DPT_Scaling
5.001
1 byte
DPT_Enumerated
5.010
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
1 bit
DPT_Bool
1.002
R
T
0 - Off; 1-On
R
T
0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
R
T
1 - Auto
R
T
1 - Heat
R
T
1 - Cool
R
T
1 - Fan
R
T
1 - Dry
R
T
%
1 - Speed 1; 2 - Speed 2; 3 Speed 3; ...; 14 Speed 14
R
T
0 – Manual; 1 - Auto
R
T
R
T
1 - Speed 1
R
T
1 - Speed 2
R
T
1 - Speed 3
R
T
1 - Speed 4
R
T
1 - Speed 5
R
T
%
1 - Position 1; 2 - Position 2; 3 Position 3;
R
T
4 - Position 4; 5 Position 5
0 – Position 1; 1 - Auto
R
T
R
T
1 - Position 1
R
T
1 - Position 2
R
T
1 - Position 3
www.abb.com/knx
Technische Helpline / Technical Support
 +49 (0) 6221 701 434 E-Mail: knx.helpline@de.abb.com
User's manual r1.5 eng
32 / 47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

2cdg 120 047 r0011

Table of Contents