ABB SM3000 User Manual page 59

Multipoint videographic recorder/paperless recorder
Hide thumbs Also See for SM3000:
Table of Contents

Advertisement

...4.3 Making Changes to Parameters – Figs. 4.4 to 4.7
Notes.
• The current, active, configuration is saved to internal storage with the filename 'SM3000.cfg'.
• Selecting 'Save as Current Configuration' suspends recording for a short time while the new configuration is
implemented.
• When saving the current configuration to internal storage, the file is saved automatically with the 'SM3000.cfg'
filename together with a <time><date><instrument tag>.cfg filename.
• When saving the current configuration to external storage, the file is saved automatically to internal storage with the
'SM3000.cfg' filename, as well as to the external archive media as <time><date><instrument tag>.cfg.
• When 'Save Configuration' is selected the configuration file is stored as <time><date><instrument tag>.cfg on
internal or external storage.
• Changes are saved to non-volatile memory only when one of the save options above has been selected. Any
powerdown before this results in lost configuration changes.
• Selecting 'Cancel' discards unsaved changes and returns the instrument to the Operating level.
• New internal data files for enabled recording channels are created if any of the following configuration parameters are
changed:
– Recording channel source
– Secondary sample rate
– Input filter type
– Channel tag
• New internal data files for all enabled recording channels are created if the instrument tag or the number of groups is
changed, or any previously disabled channel is enabled. Any unarchived data is lost.
• A warning is displayed if a configuration change will result in new internal data files for enabled recording channels
being created. Select 'Yes' to accept the configuration change. Select 'No' to cancel the configuration change.
– Primary sample rate
– Primary/secondary sample rate source
– Engineering range
Fig. 4.7 Exiting Configuration Mode
Configuration
change will
cause the internal
recording data
files to be
recreated
Configuration
change will not
cause the internal
recording data
files to be
recreated
4 CONFIGURATION...