When ①~④ is done correctly, set the parameters for communication according to the
⑤
below table.
Parameter code
< I – 60 >
< I – 61 >
< I – 62 >
< I – 63 >
Note 1) It is used for Emergency Stop when communication between inverter and master is not done
properly. It is activated when communication is not made even once for the set time. It means
remote controlling of inverter is not done. Set this value for safety.
⑥ Turn off the inverter power before the connection of the Converter when parameter
setting is finished.
4.2 Installation of communication board
① Follow the steps below for models SV004~008iC5.
Connect it to
option board
connector.
Remove
this
part
using knife
or driver.
Display
Inverter number
Baud-rate
Lost command
TimeOut (Note 1)
Supporter
Figure 2. ModBus-RTU card installation
1~32
1200~19200 [bps]
0~2
0.1 sec (Factory default)
4
MODBUS-RTU user manual
Setting Value