ABB Endura AZ30 series Programming Manual page 35

Integral probe and remote transmitter combustion oxygen monitor
Hide thumbs Also See for Endura AZ30 series:
Table of Contents

Advertisement

Endura AZ30 series integral probe and remote transmitter
Combustion oxygen monitor
Display Overview
Signals View
O2
xx.x %O2
O2
xx.x %O2
TMP
xxx °C
dT
x.x deg C/m
Back
Signals Units
Mnemonic Displayed
O2
%O2
TMP
°C or °F
dT
°C / Min or °F / Min
mV
mV
O/P
%
CJ
°C or °F
Off
mV
Fct
zOf
mV
Dev
%O2
K
d
K / Year
RT
s
RR
%O2 / s
Vac
V
Frq
Hz
Int
°C or °F
Table 6.3 Operator Menu Screens (Continued)
COI/AZ30E–EN Rev. D
Section and Function
Signals View
The Signals View displays active signals and their values as a list.
Values for signals that have not been configured are not
displayed.
Use the
Exit
Description
% Oxygen
Cell Temperature
Rate of Rise of
Cell Temperature
Cell Millivolts
Heater Output
Cold Junction Temp
Calibration Offset
Calibration Factor
Cell Zero Offset
O
Deviation
2
Cell Impedance
Cell Impedance Drift
Test Gas Response Time
Recovery Rate
Mains Voltage
Mains Frequency
Internal Temperature
and
keys to scroll through active signals.
Typical Values
0.01 to 100.00 % O
>700 °C (1292 °F)
After stabilization phase
0 to 60 °C / min
(0 to 108 °F / min)
–50 to 190 mV
0 to 100 %
–20 to 70 °C (–4 to 158 °F)
–20 mV to 20 mV
0.900 to 1.100
<20 mV
<0.5 % O
0.1 to 10.0 k
<1 k
8 to 30 s
0.05 to 0.30 % O
90 to 265 V
50 to 60 Hz
–20 to 70 °C (–4 to 158 °F)