Toshiba G9 ASD Quick Start Manual page 23

True torque control2 adjustable speed drive
Hide thumbs Also See for G9 ASD:
Table of Contents

Advertisement

Figure 4. The Grounding Capacitor
Switch is used on typeforms 230-volt
0.5 HP to 10 HP and the 25 and 30
HP/460-volt 1.0 HP to 250 HP.
The value may be set to Maximum
(default setting) or to Zero by pushing
or pulling the switch actuator,
respectively.
Figure 5. The Grounding Capacitor
Switch is used on typeforms 230-
volt 15 HP to 20 HP and the 40 HP
to 60 HP/460-volt 30 HP to 100 HP.
The value may be set to Large
(default setting) or Small by pushing or
pulling the switch actuator, respectively.
Figure 6. The Grounding Capacitor
Bar is used on typeforms 230-volt 75
HP and the 100 HP/460-volt 125 HP
and the 150 HP.
The value may be set to Large or Small
(default setting) by connecting or
disconnecting the switching bar,
respectively.
Figure 7. The Grounding Capacitor
Screw is used on typeforms 460-volt
175 HP and above.
The value may be set to Large or
Small (default setting) by placing the
screw in the A position or by placing
the screw in the B position,
respectively.
G9 ASD Quick Start Guide