[VI Q & A]
No.
Question
17
Is there a way to erase all group
registrations in one go?
18
Can a floor plan of the AE-200/AE-50
be used as a floor plan of the
TG-2000A?
19
Is there anything I can do if I have
forgotten the building manager login
password?
20
Is it possible to set the set temperature
range limit on a Mr. Slim model from
the AE-200/AE-50/EW-50 via an
M-NET adapter?
21
Are the USB memory devices that can
be used only those specified?
22
Can the set temperature range limit be
set on the system remote controller
from the AE-200/AE-50/EW-50?
23
Is an apportioned electricity billing
license required to output the billing
parameters in CSV format?
24
Can a Mr. Slim air conditioner and
LOSSNAY be interlock controlled with
the settings of the
AE-200/AE-50/EW-50?
25
The error codes of Mr. Slim are two
digits. How will they be displayed when
the Mr. Slim is connected to the
AE-200/AE-50/EW-50?
26
Is there a way to hide the inlet
temperature display of the
AE-200/AE-50 when operation is
stopped?
27
Can the power supply expansion unit
(PAC-SF46EPA) also be used without
the power supply unit
(PAC-SC51KUA)?
28
If the AE-200/AE-50/EW-50 fails after
setting the prohibit local remote
controller operation setting from the
AE-200/AE-50/EW-50, can the prohibit
local remote controller operation
setting be disabled?
29
If the power of the
AE-200/AE-50/EW-50 is shut off due
to, for example, a power failure, do the
air-conditioning units also stop?
30
I have forgotten the IP address of the
AE-200/AE-50/EW-50. How can I find
out what it is?
No, there is not.
(This function is not provided as we wish to prevent all registrations being erased by
accident.)
No, it cannot be used.
Prepare them separately because the floor plans of the AE-200/AE-50 and TG-2000A
differ in size and format.
Contact the dealer or distributor and inform them of the serial number of the
AE-200/AE-50/EW-50.
You will be given a password that allows you to log in. Log in and then change the
password.
The set temperature range limit cannot be set via an M-NET adapter.
For the settings of an MA remote controller, set them on the actual MA remote
controller.
For the settings of a ME remote controller, there is no connection via an M-NET
adapter.
For AE-200/AE-50, select a USB memory device that meets the following conditions
and verify operation several times before use.
* Reading and writing with a memory device for which operation has not been
verified may cause an unexpected operation.
Therefore, verify operation of the memory device (during trial operation) before
use.
Do not use a USB memory device for which a data writing error has occurred.
1.
USB standard: Must be USB 2.0 compliant
2.
Format: Must be formatted in FAT32 or FAT (FAT16).
3.
Must have no security function or be able to be used without the security
function. (Depending on the security function, there may also be some USB
devices for which use is possible.)
In cases such as when data writing can still not be performed normally when a USB
memory device has been replaced with another one after a data error occurs, restart
the AE-200/AE-50 (turn the power off and then back on) and then perform the check
again with a USB memory device other than the one with which the error first occurred.
No, it cannot be set on the system remote controller.
It can be set only on local remote controllers (ME and MA).
(Depending on the model of ME remote controller, setting may not be possible.)
Yes, it is required. Data output is not possible if the license is not registered.
Output to each centralized controller from the AE-200.
Yes, they can be interlock controlled.
Furthermore, there is also the method of interlocking by directly connecting the Mr.
Slim (an MA remote controller is required) to the LOSSNAY with a LOSSNAY interlock
cable.
The models (Mr. Slim and RAC/HAC) that can be connected to the
AE-200/AE-50/EW-50 are those for which errors can be indicated by the error codes
(four digits) of the AE-200/AE-50/EW-50.
Set room temperature display to [Show during operation] in the [Unit Information] of
[Initial Settings] on the AE-200/AE-50 unit.
If [Show during operation] is selected, the indoor (inlet) temperature is not displayed
when operation is stopped.
Yes, it can.
When communication from the AE-200/AE-50/EW-50 stops, the prohibit setting is
disabled after approximately 15 minutes.
If there is a local remote controller, operation continues.
If there is not, operation stops after a maximum of 13 minutes.
AE-200/AE-50
It can be checked in [Initial Settings] - [Network] screen on the LCD screen.
EW-50
(Expansion controller) It can be checked by specifying the equipment to display in
[Initial Settings] - [Network] screen on the LCD screen.
(Standalone) There is no way to check. It can be set again by using the rotary switch
(SW1) of the unit. For the setting procedure, refer to "8-3. Quick IP address setting" in
the EW-50 Installation and Instructions Manual.
85
Answer