Fujitsu PRIMEQUEST 2000 Series Hardware Installation Manual

Hide thumbs Also See for PRIMEQUEST 2000 Series:
Table of Contents

Advertisement

FUJITSU Server
PRIMEQUEST 2000 Series
Hardware Installation Manual
CA92344-0535-06

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu PRIMEQUEST 2000 Series

  • Page 1 FUJITSU Server PRIMEQUEST 2000 Series Hardware Installation Manual CA92344-0535-06...
  • Page 2 Preface Preface This manual describes the functions and features of the PRIMEQUEST 2000 series. The manual is intended for system administrators. For details on the regulatory compliance statements and safety precautions, see the PRIMEQUEST 2000 Series Safety and Regulatory Information (CA92344-0523).
  • Page 3: Revision History

    Preface Revision History Edition Date Revised location (type) Description 2014-02-18 All pages - The edition is initialized to "01" for changing manual code 2015-02-03 Chapter 2 - Corrections 2015-05-01 All pages - PRIMEQUEST 2400E2/2800E2/2800B2 is added. 2016-05-30 All pages - PRIMEQUEST 2400E3/2800E3/2800B3 is added. 2016-11-28 All pages - Corrections...
  • Page 4: Safety Precautions

    Similarly, one space line is inserted before and after the alert statement. Only Fujitsu certified service engineers should perform the following tasks on this product and the options provided by Fujitsu. Customers must not perform these tasks under any circumstances.
  • Page 5 Preface List of important alert items This manual does not contain important alert items. Warning labels Never remove the warning labels. Warning label location (the main cabinet top) CA92344-0535-06...
  • Page 6 Preface Warning label location (the main cabinet left) Warning label location (PCI_Box) CA92344-0535-06...
  • Page 7: About This Product

    For stable operation of the PRIMEQUEST 2000 series server, use only a Fujitsu-certified optional product as an added option. Note that the PRIMEQUEST 2000 series server is not guaranteed to operate with any optional product not certified by Fujitsu. Exportation/release of this product Exportation/release of this product may require necessary procedures in accordance with the regulations of the Foreign Exchange and Foreign Trade Control Law of Japan and/or US export control laws.
  • Page 8 Product and service inquiries For all product use and technical inquiries, contact the distributor where you purchased your product, or a Fujitsu sales representative or systems engineer (SE). If you do not know the appropriate contact address for inquiries about the PRIMEQUEST 2000 series, use the Fujitsu contact line.
  • Page 9: How To Use This Manual

    Be sure to keep this manual in a safe and convenient location for quick reference. Fujitsu makes every effort to prevent users and bystanders from being injured and to prevent property damage. Be sure to use the product according to the instructions in this manual.
  • Page 10 Defines the PRIMEQUEST 2000 series related terms and CA92344-0541 Glossary abbreviations. Related manuals The following manuals relate to the PRIMEQUEST 2000 series. You can access these manuals at the following site: http://www.fujitsu.com/global/products/computing/servers/mission-critical/primequest/ http://manuals.ts.fujitsu.com/ Contact your sales representative for inquiries about the ServerView manuals...
  • Page 11 Description SI MegaRAID SAS 2.0 Device Driver MegaRAID SAS 9286CV-8e Installation Refer to the following URL: The Fujitsu Technology Solutions manuals server http://manuals.ts.fujitsu.com/ Modular RAID Controller Provides technical information on using SAS RAID controllers. PRAID EP400i / EP420i (D3216) LSI MegaRAID SAS 3.0 Software PRAID EP420e LSI Integrated RAID SAS 3.0 Solution...
  • Page 12: Command Syntax

    Font or symbols Meaning Example italics Title of a manual that you should refer to See the PRIMEQUEST 2000 Series Installation Manual (CA92344-0536). Window names as well as the names of Click the [OK] button. buttons, tabs, and drop-down menus in windows are enclosed in brackets.
  • Page 13 The PDF file of this manual is intended for display using Adobe® Reader® in single page viewing mode at 100% zoom. This manual shall not be reproduced or copied without the permission of Fujitsu Limited. Copyright 2014-2017 FUJITSU LIMITED CA92344-0535-06...
  • Page 14: Table Of Contents

    Preface Contents Preface ..........................................i Installation Data ..................................1 Configuration Contents of Device ..............................1 External Overview of Device ................................. 1 1.2.1 External Overview of Device (Main equipment) ........................1 1.2.2 External Overview of Device (PCI_Box) ..........................8 Installation Specifications ................................9 1.3.1 Installation specifications (PRIMEQUEST 2400E3) .......................
  • Page 15: Preface

    Earthquake Preparedness Measures ............................54 APPENDIX A Racks ...................................... 55 A.1 Rack Mounting ..................................... 56 A.2 Rack Mounting Requirements ................................56 A.2.1 Requirements for mounting in a Fujitsu 19-inch rack ......................... 56 A.2.2 Requirements for mounting in a third party's rack ........................58 CA92344-0535-06...
  • Page 16 Preface Figures FIGURE 1.1 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2 front view ................... 2 FIGURE 1.2 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2 rear view.................... 2 FIGURE 1.3 PRIMEQUEST 2400E/2800E front view ........................... 3 FIGURE 1.4 PRIMEQUEST 2400E/2800E rear view ..........................3 FIGURE 1.5 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2/2400E/2800E top view ..............4 FIGURE 1.6 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2/2400E/2800E right side view ............
  • Page 17 Preface FIGURE 2.22 PRIMEQUEST 2400E3/2400E2/2400E (High-efficiency/Standard) 200V Redundant (N+1) ........43 FIGURE 2.23 PRIMEQUEST 2400E3/2400E2/2400E (High-efficiency/Standard) 200V Dual Power feed ........44 FIGURE 2.24 PRIMEQUEST 2400E3 with Memory Scale-up Board/2800E3/2800B3/2400E2 with Memory Scale-up Board/2800E2/2800B2/2800E/2800B (High-efficiency/Standard) 200V Non-redundant ............45 FIGURE 2.25 PRIMEQUEST 2400E3 with Memory Scale-up Board/2800E3/2800B3/2400E2 with Memory Scale-up Board/2800E2/2800B2/2800E/2800B (High-efficiency/Standard) 200V Redundant (N+1) ............
  • Page 18 TABLE 2.5 Characteristic Condition of Distribution Panel Breaker ..................... 53 TABLE 3.1 Elevator load conditions ..............................54 TABLE A.1 Recommended racks for mounting ........................... 56 TABLE A.2 PRIMEQUEST 2000 series external dimensions......................56 TABLE A.3 Structural condition of rack ..............................58 xvii...
  • Page 19: Installation Data

    CHAPTER 1 Installation Data Installation Data It explains the various data used while installing various drawings for device configuration, device overview, installation specification and layout. Configuration Contents of Device It shows the name and contents of configuration of each device. TABLE 1.1 Name and Contents of Configuration of Each device Equipment Name Content Configuration...
  • Page 20: Figure 1.1 Primequest 2400E3/2800E3/2400E2/2800E2 Front View

    CHAPTER 1 Installation Data PRIMEQUEST 2400E3/2800E3/2400E2/2800E2/2400E/2800E FIGURE 1.1 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2 front view FIGURE 1.2 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2 rear view CA92344-0535-06...
  • Page 21: Figure 1.3 Primequest 2400E/2800E Front View

    CHAPTER 1 Installation Data FIGURE 1.3 PRIMEQUEST 2400E/2800E front view FIGURE 1.4 PRIMEQUEST 2400E/2800E rear view CA92344-0535-06...
  • Page 22: Figure 1.5 Primequest 2400E3/2800E3/2400E2/2800E2/2400E/2800E Top View

    CHAPTER 1 Installation Data FIGURE 1.5 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2/2400E/2800E top view FIGURE 1.6 PRIMEQUEST 2400E3/2800E3/2400E2/2800E2/2400E/2800E right side view CA92344-0535-06...
  • Page 23: Figure 1.7 Primequest 2800B3/2800B2 Front View

    CHAPTER 1 Installation Data PRIMEQUEST 2800B3/2800B2/2800B FIGURE 1.7 PRIMEQUEST 2800B3/2800B2 front view FIGURE 1.8 PRIMEQUEST 2800B3/2800B2 rear view CA92344-0535-06...
  • Page 24: Figure 1.9 Primequest 2800B Front View

    CHAPTER 1 Installation Data FIGURE 1.9 PRIMEQUEST 2800B front view FIGURE 1.10 PRIMEQUEST 2800B rear view CA92344-0535-06...
  • Page 25: Figure 1.11 Primequest 2800B3/2800B2/2800B Top View

    CHAPTER 1 Installation Data FIGURE 1.11 PRIMEQUEST 2800B3/2800B2/2800B top view FIGURE 1.12 PRIMEQUEST 2800B3/2800B2/2800B right side view CA92344-0535-06...
  • Page 26: External Overview Of Device (Pci_Box)

    CHAPTER 1 Installation Data 1.2.2 External Overview of Device (PCI_Box) Device External Overview (Front view, Rear view, Top view, Right side view) of PCI_Box is shown below. FIGURE 1.13 Front View of PCI_Box FIGURE 1.14 Rear View of PCI_Box FIGURE 1.15 Top View of PCI_Box FIGURE 1.16 Right Side View of PCI_Box CA92344-0535-06...
  • Page 27: Installation Specifications

    CHAPTER 1 Installation Data Installation Specifications This section explains installation specification of each model. 1.3.1 Installation specifications (PRIMEQUEST 2400E3) TABLE 1.2 Installation Specifications (PRIMEQUEST 2400E3) Item Contents External Width 445(17.52) Dimensions Length(*1) 782(30.79) [mm(in.)] Height 438(17.25) 10U Mass [kg(lb)] (*2) When Memory Scale- up Board is not mounted:...
  • Page 28 CHAPTER 1 Installation Data Item Contents 5.52 kW/5.69 kVA High efficiency When Memory Scale- Power supply(*13) up Board is not mounted: 3.75 kW/3.87 kVA When Memory Scale- up Board is mounted: 5.35 kW/5.52 kVA Input Voltage: Interruptible Power 4.10 kW/4.23 kVA AC100-120V Supply(*13) Standby time...
  • Page 29: Installation Specifications (Primequest 2800E3)

    CHAPTER 1 Installation Data 1.3.2 Installation Specifications (PRIMEQUEST 2800E3) TABLE 1.3 Installation Specifications (PRIMEQUEST 2800E3) Items Contents Dimensions Width 445(17.52) [mm (in.)] Depth (*1) 782(30.79) Length 438(17.25) 10U Mass [kg (lb)] (*2) 150(331) Conditions for Max. calorific Interruptible power source 20,340(19,278) air conditioner value...
  • Page 30 CHAPTER 1 Installation Data For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F) Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained.
  • Page 31: Installation Specifications (Primequest 2800B3)

    CHAPTER 1 Installation Data 1.3.3 Installation Specifications (PRIMEQUEST 2800B3) TABLE 1.4 Installation Specifications (PRIMEQUEST 2800B3) Items Contents Dimensions Width 445(17.52) [mm (in.)] Depth (*1) 782(30.79) Length 438(17.25) 10U Mass [kg (lb)] (*2) 143(315) Conditions for Max. calorific value Interruptible power source 19,872(18,835) air conditioner [kJ/h (BTU/h)]...
  • Page 32 CHAPTER 1 Installation Data *6: Downtime is the condition in which the device is packed and maintained. *7: Level of noise which is actually heard varies as per the mounting condition of the position from where the noise is heard or the position of rack. *8: Level of noise and the level of acoustic power changes according to the Hardware configuration, the processing load and the environmental temperature.
  • Page 33: Installation Specifications (Primequest 2400E2)

    CHAPTER 1 Installation Data 1.3.4 Installation specifications (PRIMEQUEST 2400E2) TABLE 1.5 Installation Specifications (PRIMEQUEST 2400E2) Item Contents External Width 445(17.52) Dimensions Length(*1) 782(30.79) [mm(in.)] Height 438(17.25) 10U Mass [kg(lb)] (*2) When Memory Scale- up Board is not mounted: 128(282) When Memory Scale- up Board is mounted: 150(331) Conditions for...
  • Page 34 CHAPTER 1 Installation Data Item Contents up Board is mounted: 5.41 kW/5.58 kVA Input Voltage: Interruptible Power 4.10 kW/4.23 kVA AC 100-120V Supply(*13) Standby time 0.079kW Power Factor(*10) 0.95 or more Inrush current[A][Rush time](*11) 20 or less Leak current[mA](*12) 6.8 or less at AC200- 240V 3.5 or less at AC100- 120V...
  • Page 35: Installation Specifications (Primequest 2800E2)

    CHAPTER 1 Installation Data 1.3.5 Installation Specifications (PRIMEQUEST 2800E2) TABLE 1.6 Installation Specifications (PRIMEQUEST 2800E2) Items Contents Dimensions Width 445(17.52) [mm (in.)] Depth (*1) 782(30.79) Length 438(17.25) 10U Mass [kg (lb)] (*2) 150(331) Conditions for Max. calorific Interruptible power source 20,340(19,278) air conditioner value...
  • Page 36 CHAPTER 1 Installation Data For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F) Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained.
  • Page 37: Installation Specifications (Primequest 2800B2)

    CHAPTER 1 Installation Data 1.3.6 Installation Specifications (PRIMEQUEST 2800B2) TABLE 1.7 Installation Specifications (PRIMEQUEST 2800B2) Items Contents Dimensions Width 445(17.52) [mm (in.)] Depth (*1) 782(30.79) Length 438(17.25) 10U Mass [kg (lb)] (*2) 143(315) Conditions for Max. calorific value Interruptible power source 19,872(18,835) air conditioner [kJ/h (BTU/h)]...
  • Page 38 CHAPTER 1 Installation Data *6: Downtime is the condition in which the device is packed and maintained. *7: Level of noise which is actually heard varies as per the mounting condition of the position from where the noise is heard or the position of rack. *8: Level of noise and the level of acoustic power changes according to the Hardware configuration, the processing load and the environmental temperature.
  • Page 39: Installation Specifications (Primequest 2400E)

    CHAPTER 1 Installation Data 1.3.7 Installation specifications (PRIMEQUEST 2400E) TABLE 1.8 Installation Specifications (PRIMEQUEST 2400E) Item Contents External Width 445(17.52) Dimensions Length(*1) 782(30.79) [mm(in.)] Height 438(17.25) 10U Mass [kg(lb)] (*2) 128(282) Conditions Maximum Calorific value Input Interruptible Power 15,000(14,200) for Air [kJ/h(BTU/h)] Voltage: Supply(*13)
  • Page 40 CHAPTER 1 Installation Data D=Number of mounted DU (Minimum 0 to Maximum 2) *3: If the device is overloaded or if abnormality is detected even though the recommended environmental temperature is used, the FAN rotates at high-speed. *4: Protect from condensation *5: Temperature conditions changes according to installation location above sea level.
  • Page 41: Installation Specifications (Primequest 2800E)

    CHAPTER 1 Installation Data 1.3.8 Installation Specifications (PRIMEQUEST 2800E) TABLE 1.9 Installation Specifications (PRIMEQUEST 2800E) Items Contents Dimensions Width 445(17.52) [mm (in.)] Depth (*1) 782(30.79) Length 438(17.25) 10U Mass [kg (lb)] (*2) 150(331) Conditions for Max. calorific Interruptible power source 22,000(20,900) air conditioner value...
  • Page 42 CHAPTER 1 Installation Data For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F) Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained.
  • Page 43: Installation Specifications (Primequest 2800B)

    CHAPTER 1 Installation Data 1.3.9 Installation Specifications (PRIMEQUEST 2800B) TABLE 1.10 Installation Specifications (PRIMEQUEST 2800B) Items Contents Dimensions Width 445(17.52) [mm (in.)] Depth (*1) 782(30.79) Length 438(17.25) 10U Mass [kg (lb)] (*2) 143(315) Conditions for Max. calorific Interruptible power source 21,600(20,500) air conditioner value...
  • Page 44 CHAPTER 1 Installation Data For 2000 to 3000 m (6562 to 9843 ft) above sea level, temperature range at the time of installation: 5 to 29°C (41 to 84.2°F) Error of + 100m in the sea level settings of the location of installation is permissible. *6: Downtime is the condition in which the device is packed and maintained.
  • Page 45: Installation Specifications (Pci_Box)

    CHAPTER 1 Installation Data 1.3.10 Installation Specifications (PCI_Box) TABLE 1.11 Installation Specifications (PCI_Box) Item Contents Dimensions Width 482 (18.98) [mm (in)] Depth 740 (29.13) Length 175 (6.89) 4U Mass [kg (lb)] (*2) 35 (77) Conditions Max. calorific value [kJ/h (BTU/h)] 1656 (1570) for air Displacement [m3/min...
  • Page 46 CHAPTER 1 Installation Data *9: Downtime is the condition in which the device is installed. However, the power is switched off. *10: Value at the time of operations. *11: Value of 1 input cable *12: Value of 1 device CA92344-0535-06...
  • Page 47: Installation Area

    CHAPTER 1 Installation Data Installation Area Here, the installation area and the service area when the PRIMEQUEST 2000 series or the PCI_Box is installed on 19-inch made by Fujitsu rack are explained. The installation area and the service area differ according to the installed 19-inch rack.
  • Page 48: Flow Of Cooling Air And Exhaust Air Of Installation

    CHAPTER 1 Installation Data Flow of Cooling Air and Exhaust Air of Installation Here, the flow of the cooling air and the exhaust of each device are explained. Note Flow of cooling air and exhaust air should be considered while studying the installation of a device. If device is installed without considering them, it may get affected by inhaling the exhaust air from the other device.
  • Page 49: Installation Environment

    CHAPTER 1 Installation Data Installation Environment This section describes the installation environment of the base cabinet and PCI_Box. 1.6.1 Dust Suspended Particles Suspended particles in a computer room should not exceed 0.15mg/m . A computer is designed in such a way that it withstands the suspended particles.
  • Page 50: Connected Information

    CHAPTER 2 Connected Information Connected Information This section describes the connection summary of cable and cable used in PRIMEQUEST 2000 series. Connection summary This section shows the Device connection summary of PRIMEQUEST 2000 series. FIGURE 2.1 Summary of Device Connection...
  • Page 51: Connection Of Signal Cable

    “PRIMEQUEST 2000 series system mounting” 2.2.2 Details of external interface connection Mounting position of external interface connecting part of PRIMEQUEST 2000 series is shown in the section below. When calculating the length of the connection cable, you should take account into the mounting position.
  • Page 52: Figure 2.2 External Interface Connection Figure Of (Primequest 2400E3/2400E2 (Front Surface))

    CHAPTER 2 Connected Information External interface connection (PRIMEQUEST 2400E3/2400E2 in base cabinet) External interface connection figure of PRIMEQUEST 2400E3/2400E2 in base cabinet is shown in the section below. The figure below is uncovered front surface (face). The front cover must be attached in normal operation. Remark Please refer to “External interface connection (PRIMEQUEST 2400E3 with Memory Scale-up Board/ 2800E3/2400E2 with Memory Scale-up Board/2800E2 in base cabinet)”...
  • Page 53: Figure 2.4 External Interface Connection Figure Of (Primequest 2400E3 With Memory Scale-Up Board/2800E3/Primequest 2400E2 With Memory Scale-Up Board/2800E2 (Front Surface))

    CHAPTER 2 Connected Information External interface connection (PRIMEQUEST 2400E3 with Memory Scale-up Board /2800E3/2400E2 with Memory Scale-up Board/2800E2 in base cabinet) External interface connection figure of PRIMEQUEST 2400E3 with Memory Scale-up Board/2800E3/2400E2 with Memory Scale-up Board/2800E2 in base cabinet is shown in the section below. This figure is uncovered front surface (face).
  • Page 54: Figure 2.6 External Interface Connection Figure Of (Primequest 2800B3/2800B2 (Front Surface))

    CHAPTER 2 Connected Information External interface connection (PRIMEQUEST 2800B3/2800B2 in base cabinet) External interface connection figure of PRIMEQUEST 2800B3/2800B2 in base cabinet is shown in the section below. This figure is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.6 External interface connection figure of (PRIMEQUEST 2800B3/2800B2 (Front surface)) FIGURE 2.7 External interface connection figure of (PRIMEQUEST 2800B3/2800B2 (Back surface)) CA92344-0535-06...
  • Page 55: Figure 2.8 External Interface Connection Figure Of (Primequest 2400E (Front Surface))

    CHAPTER 2 Connected Information External interface connection (PRIMEQUEST 2400E in base cabinet) External interface connection figure of PRIMEQUEST 2400E in base cabinet is shown in the section below. The figure below is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.8 External interface connection figure of (PRIMEQUEST 2400E (Front surface)) FIGURE 2.9 External interface connection figure of (PRIMEQUEST 2400E (Back surface)) CA92344-0535-06...
  • Page 56: Figure 2.10 External Interface Connection Figure Of (Primequest 2800E (Front Surface))

    CHAPTER 2 Connected Information External interface connection (PRIMEQUEST 2800E in base cabinet) External interface connection figure of PRIMEQUEST 2800E in base cabinet is shown in the section below. This figure is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.10 External interface connection figure of (PRIMEQUEST 2800E (Front surface)) FIGURE 2.11 External interface connection figure of (PRIMEQUEST 2800E (Back surface)) CA92344-0535-06...
  • Page 57: Figure 2.12 External Interface Connection Figure Of (Primequest 2800B (Front Surface))

    CHAPTER 2 Connected Information External interface connection (PRIMEQUEST 2800B in base cabinet) External interface connection figure of PRIMEQUEST 2800B in base cabinet is shown in the section below. This figure is uncovered front surface (face). The front cover must be attached in normal operation. FIGURE 2.12 External interface connection figure of (PRIMEQUEST 2800B (Front surface)) FIGURE 2.13 External interface connection figure of (PRIMEQUEST 2800B (Back surface)) CA92344-0535-06...
  • Page 58: Figure 2.14 Details Of External Interface (Mmb)

    CHAPTER 2 Connected Information Details of external interface (MMB) FIGURE 2.14 Details of external interface (MMB) Details of external interface (IOU_1GbE/IOU_10GbE) FIGURE 2.15 Details of external interface (IOU_1GbE) FIGURE 2.16 Details of external interface (IOU_10GbE) Details of external interface (DU) FIGURE 2.17 Details of external interface (DU) CA92344-0535-06...
  • Page 59: Power Cable Connection

    CHAPTER 2 Connected Information Details of external interface (PCI_Box) FIGURE 2.18 Details of external interface (PCI_Box) PCIC: PCI slot LNKC: LINK card Power cable connection Input power system of PRIMEQUEST 2000series and PCI_Box is described in this section. CA92344-0535-06...
  • Page 60: Power Supply Cable Connection (Primequest 2400E3/2400E2/2400E)

    CHAPTER 2 Connected Information 2.3.1 Power Supply Cable Connection (PRIMEQUEST 2400E3/2400E2/2400E) This section shows the input power system diagram of following models. - PRIMEQUEST 2400E3 - PRIMEQUEST 2400E2 - PRIMEQUEST 2400E (Standard) 100V Non-redundant It is necessary to arrange three PSUs, three FANUs and three power supply cables (100 V NEMA 5-15P) for (Standard) 100V Non-redundant.
  • Page 61: Figure 2.21 Primequest 2400E3/2400E2/2400E (High-Efficiency/Standard) 200V Non-Redundant

    CHAPTER 2 Connected Information (High-efficiency/Standard) 200V Non-redundant It is necessary to arrange two PSUs, four FANUs, two power cables (200 V IEC60320 C20) and one power distribution box (200 V IEC60320 C19×3type) for (High-efficiency/Standard) 200V Non-redundant. When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution panel.
  • Page 62: Figure 2.23 Primequest 2400E3/2400E2/2400E (High-Efficiency/Standard) 200V Dual Power Feed

    CHAPTER 2 Connected Information (High-efficiency/Standard) 200V Dual Power feed It is necessary to arrange four PSUs, two FANUs, four power cables (200 V IEC60320 C20) and two power distribution boxes (200 V IEC60320 C19×3type) for 200 V dual power feed configuration for Japan and Overseas.
  • Page 63: Power Cables Connections

    CHAPTER 2 Connected Information 2.3.2 Power Cables Connections (PRIMEQUEST 2400E3 with Memory Scale-up Board/2800E3/2800B3/2400E2 with Memory Scale-up Board/2800E2/2800B2/2800E/2800B) This section shows the input power system diagram of following models. - PRIMEQUEST 2400E3 with Memory Scale-up Board - PRIMEQUEST 2800E3 - PRIMEQUEST 2800B3 - PRIMEQUEST 2400E2 with Memory Scale-up Board - PRIMEQUEST 2800E2 - PRIMEQUEST 2800B2...
  • Page 64: Figure 2.25 Primequest 2400E3 With Memory Scale-Up Board/2800E3/2800B3/2400E2 With Memory Scale-Up

    CHAPTER 2 Connected Information (High-efficiency/Standard) 200V Redundant (N+1) It is necessary to arrange four PSUs, two FANUs, four Power cables (200 V IEC60320 C20) and two power distribution boxes (200 V IEC60320 C19×3type) for (High-efficiency/Standard) 200V Redundant (N+1). When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution panel.
  • Page 65: Power Cable Connections (Pci_Box)

    CHAPTER 2 Connected Information (High-efficiency/Standard) 200V Dual Power feed It is necessary to arrange six PSUs, six power cables (200 V IEC60320 C20) and four power distribution boxes (200 V IEC60320 C19×3type) for 200 V dual power feed configuration. When the power distribution box is used, it is necessary to secure the breaker characteristic of distribution panel.
  • Page 66: Figure 2.27 Pci_Box (Standard) 100V Non-Redundant

    CHAPTER 2 Connected Information (Standard) 100V Non-redundant It is necessary to arrange PSU and power cable (100 V NEMA 5-15P) for (Standard) 100V Non-redundant. FIGURE 2.27 PCI_Box (Standard) 100V Non-redundant Number Description Customer distribution panel AC 100V AC#0 system (Standard) 100V Redundant (N+1) It is necessary to arrange two PSUs and two power cables (100 V NEMA 5-15P) for (Standard) 100V Redundant (N+1).
  • Page 67: Figure 2.30 Pci_Box (High-Efficiency/Standard) 200V Redundant (N+1)

    CHAPTER 2 Connected Information (High-efficiency/Standard) 200V Redundant (N+1) It is necessary to arrange two PSUs, two power cables (200 V IEC60320 C14) and power distribution box (200 V IEC60320 C13×4type) for 200 V redundant power feed configuration (single power feed, redundant power supply).
  • Page 68: Connection Specifications Of Input Power

    Connection Specifications of Input Power This section describes the connection specifications of Input power of the base cabinet or PCI_Box of PRIMEQUEST 2000 series. 2.4.1 Input Power Connection Specifications (Base Cabinet) Following table shows the input power connection specifications of the main unit.
  • Page 69: 2.4.3 Power Distribution Box And Distribution Panel

    CHAPTER 2 Connected Information 2.4.3 Power Distribution Box and Distribution Panel Following table shows the power supply cable specifications of power distribution box and distribution panel. TABLE 2.4 Power Supply Cable Specifications of Power Distribution Box and Distribution Panel Destination Plug format Remarks 200V for countries...
  • Page 70: Free Access Underfloor Connection Of Power Cable

    300 mm (11.8 in) or more Recipient power distribution Remarks The above figure shows an example of 19-inch rack made by Fujitsu Limited mounted with the device. Cutoff Characteristics of Distribution Panel (At the time of connecting power distribution box)
  • Page 71: Figure 2.34 Characteristics Of Breaker Of Distribution Panel

    CHAPTER 2 Connected Information TABLE 2.5 Characteristic Condition of Distribution Panel Breaker Breaker capacity of Distribution panel Breaker Power input Device Name For Japan/general For Europe overseas/North America AC200-240V Power distribution box Cutoff characteristic is Long-time delay type and the cutoff characteristic equivalent to D (IEC898or IN0641 part II) shown in “FIGURE 2.34 Characteristics of Breaker of Distribution Panel”...
  • Page 72: Notes On Carrying In And Installing The Product

    Notes on Carrying In and Installing the Product This chapter provides notes on carrying in and installing the PRIMEQUEST 2000 series server. Elevator Load Conditions The rack with the device mounted is wider than the average computer. Therefore, to use an elevator to carry in the rack, the rack may need the side boards or doors removed before loading on the elevator.
  • Page 73: Appendix A Racks

    APPENDIX A Racks APPENDIX A Racks This appendix provides various information on the mounting racks for the PRIMEQUEST 2000 series and PCI_Box. Remarks Equipment is not lifted by the handle attached to the main part equipment right-and-left side. Please remove the steering wheel by minus driver before installing the device in the rack. installing to the rack.
  • Page 74: A.1 Rack Mounting

    The PRIMEQUEST 2000 series (including peripheral devices) has been developed and its operation guaranteed with the basic assumption that it is mounted in a Fujitsu rack. For safe use of a unit mounted in a Fujitsu rack, contact the distributor where you purchased your product, or your sales representative.
  • Page 75: Figure A.1 Example Of Rack Mounting

    Model Mounting area mountable units The bottom of the mounted device must not be below 1U. (*1) PRIMEQUEST 2000 series The top of the mounted device must not be above 1,066 mm from floor. (*2). PCI_Box No mounting requirements (*1) For the models 2742/2737/2724/2642/2624/2616 and PCR M1 742S/724S/642S/624S/616S/742A/724A, the bottom of the mounted device must not be below 2U.
  • Page 76: A.2.2 Requirements For Mounting In A Third Party's Rack

    Note Fujitsu does not guarantee there will be no problems arising from the mounting of the PRIMEQUEST 2000 series server (including peripheral devices) in a rack manufactured by another company. Examples: Cooling problem due to an insufficient supply of cooling air because of the rack structure, and...
  • Page 77: Figure A.2 Length Of Rack

    APPENDIX A Racks Length of rack FIGURE A.2 Length of rack Number Description Front cover Front post Rear post Rear cover Width of rack FIGURE A.3 Width of rack Number Description Front cover Front post Rear post Rear cover Bracket installation area Width of Bracket installation Width of chassis of PRIMEQUEST Chassis of PRIMEQUEST...
  • Page 78: Figure A.4 Format Of Rack Posts

    Securing the maintenance work area (service area) Secure the service area required for the maintenance work performed by a Fujitsu certified service engineer. Referring to the Fujitsu rack service areas in 1.4 Installation Area...