Description Of Monitor Code - Toshiba TOSVERT VF-AS1 Function Manual

Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

4.4.6.

Description of monitor code

Divide the monitor code (RWw n) into half and select the first monitor data (RWr n) from
the lower 8 bits and the second monitor data (RWr n) from the higher 8 bits.
(Example) When output voltage is selected for the first monitor and output torque is
selected for the second monitor. -> The monitor code is 0703H.
Second monitor description
Monitor code (When an invalid monitor code is set up, monitor value fixes to 0.)
Second Monitor Description
Code Number
00H
Output frequency
01H
Output frequency
02H *1
Output current
03H
Output voltage
04H
None monitor (Monitor value is 0)
05H
Frequency command value
06H
None monitor (Monitor value is 0)
07H
Output torque
08H
DC voltage
09H
PBR load factor
0AH
Motor overload factor (OL2 data)
0BH, 0CH
None monitor (Monitor value is 0)
0DH
Input power
0EH
Output power
0FH
Input terminal information
10H
Output terminal information
11H
Output current (% monitor)
12H
Exciting current
13H
None monitor (Monitor value is 0)
14H
Cumulative operation time
15H, 16H
None monitor (Monitor value is 0)
17H
Accumulation power supply ON time Accumulation power supply ON time
18H
Motor overload factor
19H
Integral input power
1AH
Integral output power
1BH
RR/S4 input
1CH
VI/II input
1DH
RX input
1EH, 1FH
None monitor (Monitor value is 0)
20H
Torque command
21H
Torque current
22H, 23H
None monitor (Monitor value is 0)
24H
PID feedback value
25H to 2FH
None monitor (Monitor value is 0)
*1: The monitor code "02H" will be overflow when its value more than 327.67A. If that monitor overflowed, use
the monitor code "11H".
RWw n
the higher 8 bits
(the higher 8 bits)
− 
Monitor code
the lower 8 bits
First monitor description
First Monitor Description
(the lower 8 bits)
None monitor (Monitor value is 0)
Output frequency
Output current
Output voltage
None monitor (Monitor value is 0)
Frequency command value
None monitor (Monitor value is 0)
Output torque
DC voltage
PBR load factor
Motor overload factor (OL2 data)
None monitor (Monitor value is 0)
Input power
Output power
Input terminal information
Output terminal information
Output current (% monitor)
Exciting current
None monitor (Monitor value is 0)
Cumulative operation time
None monitor (Monitor value is 0)
Motor overload factor
Integral input power
Integral output power
RR/S4 input
VI/II input
RX input
None monitor (Monitor value is 0)
Torque command
Torque current
None monitor (Monitor value is 0)
PID feedback value
None monitor (Monitor value is 0)
18  −
E6581288①
Unit
0.01Hz
0.01Hz
0.01A
0.1V
0.01Hz
0.1%
0.1V
0.1%
0.1%
0.01kW
0.01kW
0.1%
0.01A
1h
1h
0.1%
1kWh
1kWh
0.1%
0.1%
0.01Hz

Hide quick links: