Fault rectification
6
Alarms and faults
Number
Cause
F01033
Unit switchover: Reference parameter
value invalid
F01034
Unit switchover: Calculation of the
parameter values after reference value
change unsuccessful
F01040
Parameters must be saved
F01044
Fault loading the data from the
memory card
F01105
Insufficient memory
F01122
Frequency at the probe input too high
F01205
Time slice overflow
F01250
CU hardware fault
F01512
No scaling
F01662
CU hardware fault
A01910
Setpoint timeout: p2040 ≠ 0 ms and
one of the following causes:
F01910
The bus connection is interrupted
The MODBUS master is switched
off
Communications error (CRC,
parity bit, logical error)
F03505
Analog input, wire break
F06310
Supply voltage (p0210) incorrectly
parameterized
F07011
Motor overtemperature
F07016
Motor temperature sensor fault
F07086
Unit switchover: Parameter limit
violation
F07088
F07320
Automatic restart aborted
F07330
Search current measured too low
50
Siemens AG
Solution
3.
Recommission the drive.
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
Select the value of the reference parameter so that the parameters involved can
be calculated in the representation (p0304, p0305, p0310, p0596, p2000,
p2001, p2002, p2003, r2004).
Save the parameters (p0971).
Switch the CU off and on again.
Replace the memory card of the CU.
Reduce the number of data records.
Reduce the frequency of the pulses at the measuring input.
Contact Technical Support.
Replace the CU.
An attempt has been made to establish a conversion factor for scaling which is not
present.
Apply scaling or check the transfer value.
Switch the CU off and on again.
Update the firmware.
Contact Technical Support.
Establish the bus connection and switch on the communication partners.
Possibly adapt p2040.
Set the PROFIBUS master to RUN.
Check the connection with the signal source for interruptions.
Check the level of the signal which is fed in.
The input current measured by the analog input can be read in r0752.
Check the supply voltage and change the parameter (p0210), if necessary.
Check the line voltage.
Reduce the motor load.
Check the ambient temperature and the motor ventilation.
Check the wiring and the connection of the sensor.
Check that the sensor is correctly connected.
Check the parameter assignment (p0601).
Switch off the temperature sensor error (p0607 = 0).
Check the adapted parameter value and correct it, if necessary.
Increase the number of restart attempts (p1211). The actual number of start
attempts is shown in r1214.
Increase the waiting time in p1212 or the monitoring time in p1213.
Apply the ON command (p0840).
Increase the monitoring time of the power unit or disable the monitoring time
(p0857).
Reduce the waiting time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
Increase the search current (p1202).
CM2G5111en
2014-05-16