ABB REU615 Product Manual

ABB REU615 Product Manual

Relion 615 series voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

®
Relion
615 series
Voltage Protection and Control
REU615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REU615

  • Page 1 ® Relion 615 series Voltage Protection and Control REU615 Product Guide...
  • Page 2: Table Of Contents

    15. Current circuit supervision...........14 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.
  • Page 3: Description

    CB control, measuring and supervising can be altered by means of the graphical signal ® functions. REU615 is a member of ABB’s Relion matrix or the graphical application functionality of product family and part of its 615 protection and the Protection and Control IED Manager PCM600.
  • Page 4 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 2. Supported functions Functionality Protection Three-phase non-directional overcurrent protection, low stage, instance 1 ● Three-phase non-directional overcurrent protection, high stage, instance 1 ● Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 ●...
  • Page 5 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 2. Supported functions, continued Functionality Multi-purpose protection, instance 6 Load shedding and restoration, instance 1 ● Load shedding and restoration, instance 2 ● Load shedding and restoration, instance 3 ●...
  • Page 6: Protection Functions

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 2. Supported functions, continued Functionality RTD/mA measurement Frequency measurement ● ● = included, o = optional at the time of order The instances of a protection function represent the number of identical function blocks available in a standard configuration. By setting the application specific parameters of an instance, a protection function stage can be established.
  • Page 7 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 and the timers of the protection function can be set to operate when the input values are below or exceeds the set values. GUID-5E258DF3-B410-4FEE-9925-A8FC9C3617CE V2 EN Figure 1. Protection function overview of standard configuration A...
  • Page 8: Application

    Standard configuration A REU615 can be used for loss-of-mains (LOM) protection for single power generating units. The A configuration of REU615 is intended to be used in medium voltage switchgear, supplied with Standard configuration B a dedicated voltage measurement cubicle. The A...
  • Page 9 REU615 and REF615 are employed for busbar protection for the voltage measurement bay and related parts of the busbar. Apart from the busbar protection and supervision the REU615 IED is utilized for centralized load shedding (disconnection) and restoration (reconnection) of one of the outgoing feeders.
  • Page 10: Supported Abb Solutions

    GUID-A90B4035-68B9-4264-83C5-DD791DDEDAB0 V2 EN Figure 4. Tap changer control and power transformer thermal overload protection using REU615 with the standard configuration B. The tap changer position information is received as a mA-signal from the tap changer operation mechanism. The position value is sent to the transformer differential protection function of the RET615 IED using GOOSE messaging.
  • Page 11 MicroSCADA Pro features of COM600. The data historian can be and System 800xA used for accurate process performance monitoring by following process and equipment Table 3. Supported ABB solutions Product Version Grid Automation controller COM600 3.5 or later MicroSCADA Pro SYS 600 9.3 FP1 or later...
  • Page 12: Control

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V3 EN Figure 6. Industrial power system example using 615 series IEDs, Grid Automation controller COM600 and System 800xA 6. Control voltage and voltage phase sequence component The IED offers control of one circuit breaker with measurement.
  • Page 13: Disturbance Recorder

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 remotely using the web-browser based user record includes current, voltage and angle values, interface. time stamp, etc. The fault recording can be triggered by the start signal or the trip signal of a protection block, or by both.
  • Page 14: Current Circuit Supervision

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 15. Current circuit supervision The residual current input and the phase-current Current circuit supervision is used for detecting inputs are rated 1/5 A. The three phase-voltage faults in the current transformer secondary inputs and the residual-voltage input covers the circuits.
  • Page 15: Station Communication

    IED simultaneously. values, such as surrounding temperature values, Further, Modbus serial and Modbus TCP can be to other IED applications. In REU615 analog used in parallel, and if required both IEC 61850 GOOSE messaging is employed in control and Modbus protocols can be run simultaneously.
  • Page 16 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 connections are supported. Termination and pull- With special time synchronization wiring: up/down resistors can be configured with jumpers • IRIG-B (Inter-Range Instrumentation Group - on the communication card so external resistors Time Code Format B) are not needed.
  • Page 17 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 5. Supported station communication interfaces and protocols Interfaces/Protocols Ethernet Serial 100BASE-TX RJ-45 100BASE-FX LC RS-232/RS-485 Fibre-optic ST IEC 61850 ● ● MODBUS RTU/ASCII ● ● MODBUS TCP/IP ● ●...
  • Page 18: Technical Data

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 19. Technical data Table 6. Dimensions Description Value Width frame 177 mm case 164 mm Height frame 177 mm (4U) case 160 mm Depth 201 mm (153 + 48 mm)
  • Page 19 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 8. Energizing inputs Description Value Rated frequency 50/60 Hz ± 5 Hz Current inputs Rated current, I 1/5 A Thermal withstand capability: • Continuously 20 A • For 1 s...
  • Page 20 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 10. RTD/mA measurement (XRGGIO130) Description Value RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760) sensors 250 Ω platinum TCR 0.00385 100 Ω nickel TCR 0.00618 (DIN 43760) 120 Ω...
  • Page 21 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 12. Signal outputs and IRF output Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
  • Page 22 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 16. Station communication link, fibre-optic Connector Wave length Max. distance Fibre type Permitted path attenuation MM 62.5/125 or 50/125 1300 nm 2 km <8 dB μm glass fibre core MM 62.5/125 or 50/125...
  • Page 23 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 21. Environmental tests Description Type test value Reference Dry heat test • 96 h at +55ºC IEC 60068-2-2 • 16 h at +85ºC Dry cold test • 96 h at -25ºC IEC 60068-2-1 •...
  • Page 24 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 22. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst disturbance IEC 61000-4-18 test: IEC 60255-22-1, class III IEEE C37.90.1-2002 • Common mode 2.5 kV • Differential mode 2.5 kV...
  • Page 25 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 22. Electromagnetic compatibility tests, continued Description Type test value Reference Voltage dips and short interruptions: 30%/10 ms IEC 61000-4-11 60%/100 ms 60%/1000 ms >95%/5000 ms Power frequency immunity test:...
  • Page 26 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 25. Product safety Description Reference LV directive 2006/95/EC Standard EN 60255-27 (2005) EN 60255-1 (2009) Table 26. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007) Table 27.
  • Page 27 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Protection functions Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 x I PHHPTOC ±1.5% of set value or ±0.002 x I...
  • Page 28 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Function Value (Range) Step Start Value PHLPTOC 0.05...5.00 x I 0.01 PHHPTOC 0.10...40.00 x I 0.01 PHIPTOC 1.00...40.00 x I 0.01...
  • Page 29 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 31. Three-phase overvoltage protection (PHPTOV) main settings Parameter Function Value (Range) Step Start value PHPTOV 0.05...1.60 x U 0.01 Time multiplier PHPTOV 0.05...15.00 0.01 Operate delay time PHPTOV 40...300000 ms...
  • Page 30 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 34. Positive-sequence undervoltage protection (PSPTUV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz ±1.5% of the set value or ±0.002 x U...
  • Page 31 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 37. Negative-sequence overvoltage protection (NSPTOV) main settings Parameter Function Value (Range) Step Start value NSPTOV 0.010...1.000 x U 0.001 Operate delay time NSPTOV 40...120000 ms Table 38. Frequency protection (FRPFRQ)
  • Page 32 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 40. Thermal overload protection, two time constants (T2PTTR) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz Current measurement: ±1.5% of the set value or ±0.002 (at currents in the range of 0.01...4.00 x I...
  • Page 33 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 43. Residual overvoltage protection (ROVPTOV) main settings Parameter Function Value (Range) Step Start value ROVPTOV 0.010...1.000 x U 0.001 Operate delay time ROVPTOV 40...300000 ms Table 44. Arc protection (ARCSARC)
  • Page 34 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 48. Load shedding (LSHDPFRQ) Characteristic Value Operation accuracy f< ±10 mHz df/dt ±100 mHz/s (in range |df/dt| < 5 Hz/s) ± 2.0% of the set value (in range 5 Hz/ s <...
  • Page 35 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 50. Operation characteristics Parameter Values (Range) Operating curve type 1=ANSI Ext. inv. 2=ANSI Very. inv. 3=ANSI Norm. inv. 4=ANSI Mod inv. 5=ANSI Def. Time 6=L.T.E. inv. 7=L.T.V. inv. 8=L.T. inv.
  • Page 36 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Control functions Table 51. Synchrocheck (SECRSYN) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±1 Hz Voltage: ±3.0% of the set value or ±0.01 x U Frequency: ±10 mHz...
  • Page 37 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 52. Synchronism and energizing check (SECRSYN) main settings Parameter Values (Range) Unit Step Default Description Live dead mode -1=Off 1=Both Dead Energizing check 1=Both Dead mode 2=Live L, Dead B...
  • Page 38 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 52. Synchronism and energizing check (SECRSYN) main settings, continued Parameter Values (Range) Unit Step Default Description Maximum Syn 100...6000000 2000 Maximum time to time accept synchronizing Energizing time 100...60000...
  • Page 39 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 54. On-load tap changer control with voltage regulator (OLATCC) main settings Parameter Function Value (Range) Step Band center voltage OLATCC 0.000...2.000 x Un 0.001 Control delay time 1 OLATCC 1000...300000 ms...
  • Page 40 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Measurement functions Table 55. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz ±0.5% or ±0.002 x I (at currents in the range of 0.01...4.00 x I...
  • Page 41 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 59. Three-phase power and energy (PEMMXU) Characteristic Value Operation accuracy At all three currents in range 0.10…1.20 x I At all three voltages in range 0.50…1.15 x U At the frequency f ±1 Hz...
  • Page 42 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Supervision functions Table 62. Current circuit supervision (CCRDIF) Characteristic Value < 30 ms Operate time Including the delay of the output contact. Table 63. Current circuit supervision (CCRDIF) main settings...
  • Page 43: Local Hmi

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 20. Local HMI default single line diagram. The SLD view can also The IED is available with two optional displays, a be accessed using the web-browser based user large one and a small one. The large display is interface.
  • Page 44: Mounting Methods

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 66. Large display Rows in the view Characters per row Character size Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels) 8 or more Depending on the selected language 21.
  • Page 45: Ied Case And Ied Plug-In Unit

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 22. IED case and IED plug-in unit on the upper part of the plug-in-unit. An order For safety reasons, the IED cases for current number label is placed on the side of the plug-in measuring IEDs are provided with automatically unit as well as inside the case.
  • Page 46 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 The communication module hardware determines the available communication proto - H B U B C C A H C 1 B B N 1 X E cols. Choose the hardware from one of the rows below to define the digits # 9-10.
  • Page 47 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 H B U B C C A H B C C 1 B B N 1 Description Language English English and German English and Swedish English and Spanish English and Russian...
  • Page 48: Accessories And Ordering Data

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 24. Accessories and ordering data Table 67. Cables Item Order number Cable for optical sensors for arc protection 1.5 m 1MRS120534-1.5 Cable for optical sensors for arc protection 3.0 m 1MRS120534-3.0...
  • Page 49: Tools

    IED can be accessed either locally or Table 69. Tools Configuration and setting tools Version PCM600 2.4 SP1 or later Web-browser based user interface IE 7.0, IE 8.0 or IE 9.0 REU615 Connectivity Package 4.0 or later...
  • Page 50 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 70. Supported functions Function WebHMI PCM600 Basic/ PCM600 Engineering Engineering IED parameter setting ● ● ● Saving of IED parameter settings in the IED ● ● ● Signal monitoring ●...
  • Page 51: Terminal Diagrams

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 26. Terminal diagrams GUID-B89BFFF3-08F0-40D3-8F12-99FB21B3900F V1 EN Figure 14. Terminal diagram of standard configuration A...
  • Page 52 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 GUID-E5FA44B9-524F-4B19-A002-49D39DF6D6D5 V1 EN Figure 15. Terminal diagram of standard configuration B...
  • Page 53: References

    You will find the latest relevant information on the The Features and Application tabs contain REU615 protection IED on the product page. product related information in a compact format. GUID-2ECAAEFE-CEF1-4A31-97F4-B88FCF66DB8E V1 EN Figure 16.
  • Page 54: Functions, Codes And Symbols

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 28. Functions, codes and symbols Table 71. REU615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low PHLPTOC1 3I> (1) 51P-1 (1) stage...
  • Page 55 Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 71. REU615 functions, codes and symbols, continued Function IEC 61850 IEC 60617 IEC-ANSI Multi-purpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3)
  • Page 56: Document Revision History

    Voltage Protection and Control 1MRS757058 D REU615 Product version: 4.0 Table 71. REU615 functions, codes and symbols, continued Function IEC 61850 IEC 60617 IEC-ANSI Residual voltage measurement RESVMMXU1 Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0 Three-phase power and energy measurement...
  • Page 60 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...