Targets Menu - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

TARGETS MENU

With the CyberSentry option, the Administrator and Operator roles can initiate the Reboot Relay command.
SERVICE COMMAND
"20511" returns all settings to their factory default value. Code "101" is used to clear factory diagnostic information stored
in the non-volatile memory. If a code other than these two is entered, the command is ignored and no action is taken.
Various self-checking diagnostics are performed in the background while the C30 is running, and diagnostic information is
stored on the non-volatile memory from time to time based on the self-checking result. Although the diagnostic
information is cleared before the C30 is shipped from the factory, the user can want to clear the diagnostic information for
themselves under certain circumstances. For example, you clear diagnostic information after replacement of hardware.
Once the diagnostic information is cleared, all self-checking variables are reset to their initial state and diagnostics restart
from scratch.
SAVE VOLATILE DATA
recent as possible instead of relying on the periodic timer to save the data.
7.1.5 Security
COMMANDS  SECURITY
 SECURITY

With the CyberSentry option, this setting is available to enable or disable the following commands.
ADMINISTRATOR LOGOFF
ENGINEER LOGOFF
OPERATOR LOGOFF
CLEAR SECURITY DATA
7
operands associated with the self-tests.
7.2 Targets menu
7-4
— Performs specific C30 service actions. Presently, there are two service actions available. Code
— Saves this data to compact flash memory prior to shutdown. This allows the saved data to be as
ADMINISTRATOR
LOGOFF: No
ENGINEER
LOGOFF: No
OPERATOR
LOGOFF: No
CLEAR SECURITY DATA:
No
— Selecting 'Yes' allows the Supervisor to forcefully logoff an administrator session.
— Selecting 'Yes' allows the Supervisor to forcefully logoff an engineer session.
— Selecting 'Yes' allows the Supervisor to forcefully logoff an operator session.
— Selecting 'Yes' allows the Supervisor to forcefully clear all the security logs and clears all the
TARGETS
PHASE TOC4
OP: A B -
DIGITAL ELEMENT 48:
LATCHED
Range: Yes, No
Range: Yes, No
Range: Yes, No
Range: Yes, No
Displayed only if targets for this element are active.
Example shown.
Displayed only if targets for this element are active.
Example shown.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 7: COMMANDS AND TARGETS

Advertisement

Table of Contents
loading

Table of Contents