ABB i-bus KNX
3.2.2
"Temperature
Measurement" parameter
window
© 2009 Busch-Jaeger Elektro GmbH – A Company of the ABB Group
Commissioning
Offset for room temp. meas.
(measured value changed by (-128..127)x0.1 K)
Options:
- -128
- ...
- 0
- ...
- 127
Value range –128..127 corresponds to –12.8K..12.7K
If the actual temperature is recorded internally, it may be falsified by an
additional internal heat source, e.g. bus or network coupler. The falsified
value can be adjusted with the setting "calibration value for ambient
temperature measurement".
Setpoint larger when sending change
Options:
- Inactive
- 0.1 K
- 0.2 K
- 0.3 K
- 0.4 K
- 0.5 K
- 0.6 K
- 0.7 K
- 0.8 K
- 0.9 K
- 1.0 K
If this parameter is set to a difference, the associated 2-byte communication
object "Current temperature" sends its current temperature whenever this
parameter changes.
17