6.34.8 Cancel the operation command
f719 : Selection of operation command clear
 Function
Operation command retained :
occurs.
Operation command canceled :
[Setup example of input terminal]
When it is assigned to the RES terminal.
Setting value 7, 97 are reverse signal.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
This parameter allows you to select operation command retained or operation command canceled,
when coast stop occurs due to standby terminal function (ST) or coast stop command terminal function,
and when under voltage in main circuit alarm occurs, during panel operation or RS485 communication
operation.
Parameter
At coast stop
setting
Operation command
=
canceled
=
=
=
Inverter restarts due to canceling coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm ()
Inverter doesn't restart after coast stop or occurring the under voltage in main circuit alarm ().
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
Function
Selection of operation
f719
command clear
Title
Function
Input terminal selection 3A
f113 
(RES)
Input terminal selection 3A
f113 
(RES)
Under voltage in main circuit
alarm ( moff ) occurrence
Operation command retained
Operation command retained
Operation command canceled
Operation command canceled
Adjustment range
0: Clear at coast stop and retained at
moff .
1: Retained at coast stop and moff .
2: Clear at coast stop and moff .
3: 2+ clear when cmod is changed
Adjustment range
0-203
0-203
F-131
E6581611
comd
is changed
Operation command
retained
Default setting
1
Setting
6: ST (Standby)
96: FRR (Coast stop command)
6