Rectifier tests
Positive measuring
Negative measuring
point
point
L1
DC-
L2
DC-
L3
DC-
DC +
L1
DC +
L2
DC +
L3
DC-
L1
DC-
L2
DC-
L3
IGBT bridge test
Positive measuring
Negative measuring
point
point
U
DC +
V
DC +
W
DC +
U
DC-
V
DC-
W
DC-
How to proceed if a fault is discovered
 The variable speed drive has failed one of these tests:
Remove the Power Module (power unit) in order to replace or repair it.
 A short circuit is present at the input rectifiers or at components of the IGBT
bridge:
Check the state of fuses in the supply line, of contactors, disconnectors or of
the motor itself.
Remember that an apparently open circuit can also occur following a component
short-circuit and the resulting strong flow of current.
Service, maintenance and fault rectification
Fault rectification
Expected result
Diode block – OL/High impedance
Diode block – OL/High impedance
Diode block – OL/High impedance
Diode block – OL/High impedance
Diode block – OL/High impedance
Diode block – OL/High impedance
Diode aperture – typically 0.3 – 0.5V
Diode aperture – typically 0.3 – 0.5V
Diode aperture – typically 0.3 – 0.5V
Expected result
Diode aperture – typically 0.3...0.5 V
Diode aperture – typically 0.3...0.5 V
Diode aperture – typically 0.3...0.5 V
Diode block – OL/High impedance
Diode block – OL/High impedance
Diode block – OL/High impedance
8
OK
OK
89 | 98
A5E36496664A_d
2016-03-17