Configuration and Programming by the Engineer
8.1.3

Menu 03 "Circuits"

Engineer-PIN
8 = Edit
01 = System Size
02 = Area Opts
03 = Circuits
04 = Relay
05 = Alarm Times
06 = Keypads
07 = Concs *
08 = User Auth
09 = Text
10 = L240/B/BS*
11 = XS/1.1 KNX *
13 = 2-Conc Tamper *
15 = Defaults
16 = XIB-Detectors
8.1.3.1 Detector circuit type
Menu item "03=Circuits": In this menu, the circuit types and the properties
of the circuits of the panel and the connected detector circuit modules and
bus modules for motion detectors can be programmed.
In the default delivery state, the detector circuits 1-10 of the Intrusion Alarm
Panel are pre-programmed as:
Terminal
Detector circuit
type
Cct 1,2,3
Detector circuit
Cct 4,5,6
Detector circuit
Cct 7
Lock circuit
Cct 8
Persona attack circuit
Cct 9
Tamper circuit
Cct 10
External set
The default delivery state for the circuits, the circuit modules and the bus
modules for the motion detectors can be found in the respective chapter of
the module.
Each circuit can be reprogrammed individually. It is important to remember
that every circuit must be terminated with a terminating resistor of 2.7 kOhm.
Exceptions:
Lock circuit
It is not terminated with a resistor. A short circuit indicates a closed door
and an open circuit indicates that the door is not closed.
External set circuit
The circuit is terminated in the unset state with a 2.7 kOhm resistor. For
setting a 560 Ohm resistor is switched in series to the resistance of 2.7
kOhm (= 3.26 kOhm)
Detector circuit type
You can select 14 different circuit types. Every circuit type has determined
basic settings and different properties. The circuit types appear if during the
flashing display of the preset circuit type the
><
the
buttons you can page through the list of circuit types.
the two-digit number, the circuit is selected and applied.
01=NA
02=Tamper
03=PA
04=Lock
05=ER
06=EnEx
07=Tech Alm
08=Fire
09=Cct Off Menu
10=Cct Rst
11=Eng Rst
12=Int Set
Property
Remark:
Int Set Off=On
Circuit is not active
Ext Set Off=Off
with internal setting
Int Set Off=Off
Circuit is active with
Ext Set Off=Off
internal and external
setting
Pulse=On
Circuit is always
active
Circuit is always
active
?
button is kept pressed. With
By entering
50