8-4. Check codes displayed on remote controller and SMMS outdoor unit (7-segment
display on I/F board) and locations to be checked
For other types of outdoor units, refer to their own service manuals.
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
E01
E02
E03
E04
No. of indoor
units from
which signal is
received
normally
E06
E06
E07
Duplicated
indoor address
E08
E08
E09
E10
Location
Description
of
detection
Remote
Indoor-remote
controller
controller
communication
error
(detected at
remote
controller end)
Remote
Remote
controller
controller
transmission
error
Indoor unit
Indoor-remote
controller
communication
error
(detected at
indoor end)
Indoor unit
Indoor-outdoor
communication
circuit error
(detected at
indoor end)
I/F
Dropping out of
indoor unit
I/F
Indoor-outdoor
communication
circuit error
(detected at
outdoor end)
Indoor unit
Duplicated
I/F
indoor address
Remote
Duplicated
controller
master remote
controller
Indoor unit
Indoor inter-
MCU
communication
error
IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
Indoor unit (including Hot Water Module)
Error detection
System status
condition(s)
Stop of
Communication between
corresponding
indoor P.C. board and
unit
remote controller is disrupted.
Stop of
Signal cannot be transmitted
corresponding unit
from remote controller to
indoor unit.
Stop of
There is no communication
corresponding unit
from remote controller
(including wireless) or
network adaptor.
Stop of
Indoor unit is not receiving
corresponding unit
signal from outdoor unit.
All stop
Indoor unit initially
communicating normally fails
to return signal for specified
length of time.
All stop
Signal cannot be transmitted
from outdoor to indoor units
for 30 seconds continuously.
All stop
More than one indoor unit is
assigned same address.
Stop of
In two remote controller
corresponding unit
configuration (including
wireless), both controllers
are set up as master.
(Header indoor unit is shut
down with alarm, while
follower indoor units
continue operating.)
Stop of
Communication cannot be
corresponding unit
established / maintained
upon turning on of power or
during communication.
– 46 –
Check items (locations)
• Check remote controller
inter-unit tie cable (A / B).
• Check for broken wire or
connector bad contact.
• Check indoor power supply.
• Check for defect in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
• Check internal
transmission circuit of
remote controller.
--- Replace remote
controller as necessary.
• Check remote controller
and network adaptor wiring.
• Check order in which
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor termination
resistance setting (SW30,
Bit 2).
• Check power supply to
indoor unit.
(Is power turned on?)
• Check connection of
indoor-outdoor
communication cable.
• Check connection of
communication connectors
on indoor P.C. board.
• Check connection of
communication connectors
on outdoor P.C. board.
• Check for defect in indoor
P.C. board.
• Check for defect in outdoor
P.C. board (I/F).
• Check outdoor termination
resistance setting (SW30,
Bit 2).
• Check connection of
indoor-outdoor
communication circuit.
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group /
individual) since indoor
address setting.
• Check remote controller
settings.
• Check remote controller
P.C. boards.
• Check for defect in indoor
P.C. board