Electrically Testing The Unit - Samsung RC090-120-140 Installation And Maintenance Manual

Air source heat pump
Table of Contents

Advertisement

Electrically testing the unit:

It is possible to test each component one after another using a service function. You can use
this to make sure you have wired everything correctly.
To access service mode press
button to close it. 2-1 will show on the screen, Press top right to open it again.
To test the external run signal or stat is connected
adjust temperature on stat up.
Heat1 will replace test on screen.
Using the
blue view
button you can see 5
temperature sensors, inlet and outlet to the heat
exchanger, the red sensor (where used), water
cylinder and sensor in the remote controller.
To exit service mode press and hold cancel
delete for 6 seconds
blue
set button
and
test button together for 6 seconds.
The controller will display TEST. Immediately press the
top left button to turn the pump on and leave it running
while in test mode to avoid a fault.
Press the top left button the unit will run the pump.
Press weekly to test the immersion heater in the hot
water cylinder.
The hot water valve should be closed, Press the lock
button to make a coke can appear the HW valve should
move to open, press lock again to close it.
The Heating valve will be open, Press the top right
www.samsungehs.co.uk
©G Hendra April 2015
14