Removal Of Drain Hose - Daikin Quaternity FTXG09HVJU Service Manual

Inverter pair wall mounted type h-series
Hide thumbs Also See for Quaternity FTXG09HVJU:
Table of Contents

Advertisement

Indoor Unit
1.9

Removal of Drain Hose

Procedure
Step
1. Removal of the drain hose
1
Remove the screws of the
main unit and installation
plate.
2
Lift the main unit slightly
and remove the drain
hose, in case of piping as
shown in figure on the
right.
2. How to change drain piping
to the left
1
Detach the drain plug on
the left.
186
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Points
 Cover the drain hose with
plastic bags or the like so the
remaining drainage will not
wet the floor.
 Part A is fixed by the screw
from back side. When
replacing the hose, make sure
to tighten a screw as there is
no gap between the heat
(R10176)
insulator and the hose.
Removal Procedure
SiUS04-921