WARNING: Danger of electrical shock or injury.
Turn OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
not remove circuit protective devices or any
other component until the power is turned
OFF.
General
These instructions apply to the following catalog numbers:
• Circuit breaker modules AMC6EB, AMC4EB,
AMC6EL, AMC6EBS, AMC4EBS, and AMC4SE
• Circuit breaker frames TEB, TED, THED, TEL,
SEDA, SEHA, SELA, and SEPA
Installation
1. Phase balancing for two-pole devices on three-phase
systems. To balance the panelboard load, remove the
screws on the appropriate bus clip, reposition the bus
clip as shown in Figure 1, then install and tighten the
screws to 27–32 in-lb.
Figure 1. Repositioning the bus clip to balance the load.
2. Prepare the module. Remove the protective caps or
insulating tape only from the tops of the stud posts to
which the circuit breaker is to be attached, as shown
in Figure 2. Fasten the filler supports, as shown in
Figure 3, with #10-32 x
to 15–20 in-lb.
Spectra Series™ Power Panelboards
Circuit Breakers and Modules
.
A & C Phase
As Received
A & B Phase
B & C Phase
3
/
" hex-head screws tightened
4
GEH5625 Installation Instructions
Protective Cap
or Insulating
Tape
Do
Figure 2. Removing the cap or tape from the stud posts of the
3
#10-32 x
/
"
4
Hex-Head
Screw
Figure 3. Attaching the filler breaker module.
3. Install the circuit breaker. Remove the lug cover, if
present. Place the
posts, as shown in Figure 4. Secure the breaker to the
module with #10-32 screw and washer assemblies and
3
#8-32 x 2
/
" screws with cup washers. After all screws
4
are in place, tighten the #10-32 screws to 27–32 in-lb
and the #8-32 screws to 15–20 in-lb. Replace the lug
cover, if present.
Stud Post
breaker module.
Filler
Support
side of the breaker over the stud
ON
R04

Advertisement

loading

Summary of Contents for GE Spectra Series AMC6EB

  • Page 1 GEH5625 Installation Instructions Spectra Series™ Power Panelboards Circuit Breakers and Modules WARNING: Danger of electrical shock or injury. Turn OFF power ahead of the panelboard or Protective Cap or Insulating switchboard before working inside the Tape equipment or removing any component not remove circuit protective devices or any other component until the power is turned OFF.
  • Page 2 For double-branch devices, repeat this procedure for 5. Install the module. Latch one side of the circuit the second breaker. Combinations of circuit breaker breaker module. Release the rail latch. Pivot the types TEB, TED, THED, SEDA, SEHA, SELA, or module onto the bus bars and engage the second SEPA may be used.
  • Page 4 Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company. GE Industrial Systems General Electric Company 41 Woodford Ave., Plainville, CT 06062...

This manual is also suitable for:

Spectra series amc4ebSpectra series amc6elSpectra series amc6ebsSpectra series amc4ebsSpectra series amc4seSpectra series teb ... Show all