Siemens PTX6.H Installation Instructions

Termination block

Advertisement

Quick Links

Termination Block
Product Description
The Point Termination Module (PTM) consists of a
termination block and an electronic point module.
The termination block provides the wire connection
between the Modular Building Controller (MBC) or
Remote Building Controller (RBC) and the field input
or output device.
These procedures apply to termination block
installation only. See Installation Instructions
(545-405) for point module installation.
Product Numbers
Termination block part numbers end with an H or L
to indicate high or low voltage.
PTX6.H Replacement High Voltage Termination
Block
PTX6.L
Replacement Low Voltage
Termination Block
See Installation Instructions (545-406) for the
Replacement AO-P Termination Block (545-020)
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedures as
specified.
Required Tools
None
Expected Installation Time
3 minutes per termination block (not including wiring)
Prerequisites
MBC/RBC installed.
Job layout sheet.
A high/low voltage wire barrier may be
required by local codes. See Figure 1 and
Installation Instructions (545-420).
Item Number: 545-404-06, Rev. 010
Installation Instructions
Installations Requiring CE Compliance
or the Equivalent
All termination block wiring must be twisted, shielded
pair cable. Follow the normal specification for BLN
and FLN network cables in the APOGEE Automation
Configuration and Sizing Guidelines on InfoLink.
Any permanently installed MMI cables must be
shielded cabling.
1.
Locate one or more acceptable locations for
terminating the shields of the I/O and MMI cables:
The mounting studs of the backplane, or any
location that is both earth grounded and
within 15 cm (6 inches) of the backplane,
are acceptable.
If the backplane studs are not used, the
ground must be terminated directly to the
cabinet using self-tapping screws.
2.
Peel back the insulation of the I/O cables to expose
the correct length of shield and terminate the shield
at the proper ground locations.
Figure 1. Termination Blocks Installed in MBC.
Document No. 545-404
December 17, 2003
Page 1 of 2

Advertisement

loading

Summary of Contents for Siemens PTX6.H

  • Page 1 Termination block part numbers end with an H or L are acceptable. to indicate high or low voltage. • If the backplane studs are not used, the PTX6.H Replacement High Voltage Termination ground must be terminated directly to the Block cabinet using self-tapping screws. PTX6.L...
  • Page 2 Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Other product or company names mentioned herein may be trademarks of their respective owners. © 2003 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc.