ABB SMISSLINE TP ZLS224 Mounting Instruction

Incoming terminal block standard, incoming terminal block oversize

Advertisement

Quick Links

U L d a t a
For all types:
Feeder Blocks cat. nos. ZLS250 – ZLS253, ZLS954UL, ZLS959UL are suitable for use in feeder circuits up to 600 V
Wire required to be fixed 2 inches (50.0 mm) below entry point of component housing by suitable cable ties
Rated Voltage:
Rated Current (side feed, left or right):
Rated Current (center feed):
Short Circuit Rating:
Short Circuit Protection:
Torque:
Stripping length:
Wire size:
Wire rated min. 600 V and 75 °C (AVLV2/8)
Montage Einspeiseblock, Einspeise element
Fig. 1
Demontage Einspeiseblock, Einspeise element
Fig. 2
Montage der Hilfsklemmen LA und LB
Einspeiseblock
Fig. 3
Einspeisebeispiele
Fig. 4–10
Der IP Schutz muss durch den Errichter erstellt
werden.
Montage sur les socles, Bloc d'alimen-
tation, Elément d'alimentation
Fig. 1
Démontage, Bloc d'alimen tation, Elément
d'alimentation
Fig. 2
Montage des bornes auxiliaires LA et LB Bloc
d'alimen tation
Fig. 3
Exemples d'alimentation
Fig. 4–10
La protection de la propriété intellectuelle doit
être créé par l'installateur.
Assembly to plug-in socket system,
Incoming Terminal Block standard,
Incoming Terminal Block oversize
Fig. 1
Disconnection, Incoming Terminal Block
standard, Incoming Terminal Block oversize
Fig. 2
Assemble auxiliary terminals LA and LB Incoming
Terminal Block standard
Fig. 3
Supply variants
Fig. 4–10
La protection de la propriété intellectuelle doit
être créé par l'installateur.
max. 125 A
max. 250 A (UL+IEC), same cable length
ABB Switzerland Ltd
Low Voltage Products
Fulachstrasse 150
CH-8201 Schaffhausen
Phone: +41 58 586 41 11
Fax:
+41 58 586 42 22
www.abb.com
600 V AC
125 A
250 A max. when used with two feeder blocks
50 kA, max. 480 VAC and 480 Y/277 V and 240 VAC
150 A Fuse or Circuit-Breaker (DIVQ/7) with maximum rating
of 250 A, located at Line Side
2.0 Nm
21 mm
2 AWG - 1/0 AWG
F
max. 125 A (UL+IEC)
G
max. 125 A
max. 125 A
max. 125 A
8
ABB Inc.
8155 T&B Blvd.
Memphis, TN 38125
Technical Support:
E-Mail: lvps.support@us.abb.com
Phone: 1-888-385-1221 Option 1
For all types:
Feeder Blocks cat. nos. ZLS224, ZLS224R, ZLS225 and ZLS225R are suitable for use in feeder circuits up to 250 V
Rated Voltage:
Rated Current (side feed, left or right):
Rated Current (center feed):
Short Circuit Rating:
Short Circuit Protection:
Torque:
Stripping length:
Wire size:
Wire rated min. 600 V and 75 °C (AVLV2/8)
1
2
1
max. 125 A
max. 125 A
max. 125 A
max. 250 A (UL+IEC)
max. 125 A
max. 150 A (UL)
max. 200 A (IEC)
250 V AC
125 A
250 A max. when used with two feeder blocks
50 kA, max. 240 VAC
150 A Fuse or Circuit-Breaker (DIVQ/7) with maximum rating
of 250 A, located at Line Side
4.0 Nm
18 mm
10 AWG - 1/0 AWG
1
2
max. 125 A
max. 150 A (UL)
max. 160 A (IEC)
4
max. 125 A (UL)
6
max. 125 A
max. 125 A
max. 250 A (UL+IEC)
9
3
max. 125 A
5
7
max. 125 A
max. 125 A
10

Advertisement

loading

Summary of Contents for ABB SMISSLINE TP ZLS224

  • Page 1 125 A max. 125 A max. 150 A (UL) max. 200 A (IEC) max. 250 A (UL+IEC), same cable length max. 250 A (UL+IEC) ABB Switzerland Ltd Low Voltage Products ABB Inc. Fulachstrasse 150 8155 T&B Blvd. CH-8201 Schaffhausen...
  • Page 2 Utiliser exclusivement les barres collectrices à surface Faulty products should be treated as hazardous waste améliorée de ABB. Ne procéder à aucune sorte de ré- and disposed of in an appropriate manner. National or paration sur le système de socle d’enfichage.

This manual is also suitable for:

Smissline tp zls224rSmissline tp zls225Smissline tp zls225rSmissline tp zls250Smissline tp zls253Smissline tp zls954ul ... Show all