Room hygrostats for relative humidity

Advertisement

Quick Links

Use
Type summary
CE1N1518en
2014-07-30
QFA1001
Room Hygrostats
for relative humidity
• Hygrostat with single-pole microswitch
• Humidity measuring element made of stabilized plastic texture
• Setpoint knob for the upper switching point
• For controlling humidification equipment
• For controlling dehumidification equipment
• For mounting directly on the wall or on a recessed conduit box
The room hygrostats are used for controlling and monitoring relative humidity in ventila-
tion or air conditioning plant.
They ensure room humidity control within the selectable range of 30 to 90 % relative
humidity by controlling humidification or dehumidification equipment.
They can also be used for monitoring minimum or maximum humidity levels.
Type
Setpoint setting
reference
range
QFA1000
30...90 % r. h.
QFA1001
30...90 % r. h.
1)
The static switching differential is determined at a constant ambient humidity by turning the setting
knob.
The dynamic switching differential is determined by changing the ambient humidity while maintain-
ing the same setpoint adjustment; only the dynamic switching differential is of practical value.
QFA1000
Switching differential
Statically
Dynamically
Approx. 4 % r.h.
Approx. 4 % r.h.
Building Technologies
1
518
QFA1...
1)
Setpoint
knob
6 % r.h.
Internally
6 % r.h.
Externally

Advertisement

loading

Summary of Contents for Siemens QFA1 Series

  • Page 1 QFA1001 QFA1000 QFA1… Room Hygrostats for relative humidity • Hygrostat with single-pole microswitch • Humidity measuring element made of stabilized plastic texture • Setpoint knob for the upper switching point • For controlling humidification equipment • For controlling dehumidification equipment •...
  • Page 2 The cover carries the removable setpoint knob with its imprinted scale. QFA1000 This model is of the same basic design as the QFA1001, but there is no external setpoint knob. The setpoint can only be adjusted when the cover is removed. Siemens Room hygrostats QFA1001, QFA1000 CE1N1518en Building Technologies...
  • Page 3 Fuse slow max. T5A Protection degree of housing IP20 according to EN 60529 Degree of protection Protection class II according to EN 60730-1 Electrical connection Screw terminals for max. 2 x 1.5 mm Siemens Room hygrostats QFA1001, QFA1000 CE1N1518en Building Technologies 2014-07-30...
  • Page 4 CE1T1518xx EU Conformity (CE) Weight QFA1001 0.090 kg QFA1000 0.090 kg 1) Can be improved by recalibrating on site 2) The documents can be downloaded from http://siemens.com/bt/download. Connection diagrams Internal diagram ϕ Humidification Dehumidification Connection diagrams Diagram 1: Humidification Diagram 2: Dehumidification ϕ...

This manual is also suitable for:

Qfa1001Qfa1000