GEH-4776 Installation Instructions for NEMA Size 2
300/400 -Line Combination Magnetic Starters
CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408
CR410-CR415, CR487, CR490, CR492, CR494 Series
CAUTION:
Before installing in a nuclear
application, determine that the product is
intended for such use.
WARN ING:
Disconnect
power before Installing or
servicing.
RATINGS
Max.
Max.
AC Volts
Volt-
Continous
age
Amp
Rating
600
45
115
200
230
460/575
DESCRIPTI ON
A ABB 300-Line full voltage magnetic c o
mbination starter consists of a magnetic c
ontactor with a three leg block overload
relay and a manually operated circuit
breaker or disconnect switch. The
disconnect switch may either be fusible or
non-fusible. The non-fusible disconnect
switch prov ides a means of manually
disconnecti ng the motor from the line. The
circuit break er or fusible disconnect switch
provides m otor branch short-circuit
protection. The overload relay provides,
motor prote ction against running and
stalled mot or overload.
s
These instructions do not purport to cover all details or variations in equipment not to provi de for every possible contingency to
be met in connection with installation, operation or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser's purpose, the matter should be referred to the ABB
Company.
The overload relay is provided with a
yellow trip indicator which is located to
the right of the reset arm, and is visible
when the overload relay is tripped.
Max.Hp
For AC Motors
Single-
Poly-
Phase
Phase
3
-
-
10
15
-
25
FEATURES
1. Strongbox coil.
2. Overload relay, incorporates a dial for
±10% field adjustment of tripping current,
so that it is no longer necessary to change
heaters to eliminate such problems as
nuisance tripping in hot weather.
3. Overload trip indicator.
4. Straight through wiring.
5. Oversized power terminals will
accommodate up to #4 wire.
6. Starter can be disassembled and
inspected in a matter of seconds.
7.Circuit breaker or disconnect switch is
mechanically interlocked with the
enclosure door to prevent opening the door
until the handle is moved to the OFF
position.
INSTALLATION
Before connecting the starter:
1. Remove all packing.
2. Clean magnet mating surfaces
of any dust or foreign matter.
3. Select heaters in accordance
with heater table, which
accompanies each device.
4. Operate movable magnet and
operating arm by pressing on the
nameplate to assure free
movement.
5. Mount the starter on a sturdy
vertical support.
6. The overload relay may be reset
manually by depressing and
releasing the reset arm. Overload
relays with an optional normally
open contact are electrically
isolated from the normally closed
contact.
7. Provide motor branch circuit
protection in accordance with the
National Electrical Code.
COIL REMOVAL
The encapsulated coil is impervious
to moisture, dirt, and oil. It resists
mechanical damage and failure due
to high humidity. No tools are
required to remove coil.
1. Remove power from device.
2. Press against coil while pulling up
slightly on coil retainers (A—Figure 1
or 2) and move retainers away from
coil.
3. Withdraw magnet assembly, coil,
molded cover, and movable arm
from device.
4. Withdraw spring clip (B—Figure 1
or 2) and remove armature from
movable arm.
5. Remove coil from magnet.
6. Replace coil.
7. Reassemble device by reversing
procedure.
CONTACT REMOVAL
Movable contacts can be inspected
and replaced in seconds—without
tools (Figure 3).

Advertisement

loading

Summary of Contents for GE CR307-CR308 Series

  • Page 1 GEH-4776 Installation Instructions for NEMA Size 2 300/400 -Line Combination Magnetic Starters CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408 CR410-CR415, CR487, CR490, CR492, CR494 Series CAUTION: The overload relay is provided with a 2. Clean magnet mating surfaces Before installing in a nuclear yellow trip indicator which is located to of any dust or foreign matter.
  • Page 2 — — ABB Inc. We reserve all rights in this document and GE is a trademark of GE. Manufactured We reserve the right to make technical 305 Gregson Drive by ABB Inc. under license from GE. changes or modify the contents of this in the subject matter and illustrations Cary, NC 27511.

This manual is also suitable for:

400 series300 seriesCr310-cr311 seriesCr387 seriesCr390 seriesCr407 series ... Show all