Honeywell Eclipse 90 Quick Start Manual

Uv scanner

Advertisement

Quick Links

Introduction
This sensor features a high sensitivity ultraviolet (UV)
tube for monitoring gas or oil flames that cycle on and off
frequently. It is protected against reverse connection. The
Eclipse flame safeguard checks for a short-circuited, or
"runaway" scanner at the beginning and end of each
flame cycle. The scanner is UL listed for USA and
Canada, and is FM approved. This product is also in
conformance with the "CE Mark" directives when used
with the model VF56 Veri-Flame CE as listed in Instruction
Manual 818-2. It comes with a 10 ft (305 cm) lead. The 90°
UV Scanner operates with 5600 and VF56 series Veri-
Flames, the 6000 Series Multi-Flame and 6500 Series Bi-
Flame controllers, or series 7000 Peek-A-Flame.
The UV tube is made of quartz and is filled with a gas that
surrounds two electrodes. These electrodes
energized continuously by a high voltage. The gas acts as
an insulator in the absence of UV radiation. Combustion
produces UV radiation to ionize the gas and causes
current pulses to flow between the electrodes. These
current pulses result in a flame signal which is transmitted
to the amplifier in the control, where it is processed to
energize and hold in the flame relay.
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170.
website:
Line ID: @add11 e-mail: add028883472@gmail.com
C
US
are
https://www.add-furnace.com/
Eclipse 90°
UV Scanner
Specifications
Parameter
Part Number
49600-90
Spectral Response
185 to 260nm
Supply Voltage
425 VDC ± 25 VDC
Discharge Current
0.1 mA
Supply Wiring
10 ft (305 cm) flexible 3/8" metal
conduit with two #18 AWG
conductors
Temperature Range 0° to 140° F (-20° to +60° C)
Temperature Scanner
450° F (230° C)
Support Lens
Materials
Aluminum housing. Plated steel
conduit.
Weight
0.6 lbs (270 grams)
Options
Magnifying lens (Part #49600-
98) or 1/2" insulated coupling
(Part #49099), Scanner support
replacement (Part #20722)
โทร: 02-888-3472
Model 5600-90A
Version 2
Specification

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Eclipse 90

  • Page 1 44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170. website: https://www.add-furnace.com/ โทร: 02-888-3472 Line ID: @add11 e-mail: add028883472@gmail.com Eclipse 90° UV Scanner Model 5600-90A Version 2 Introduction Specifications This sensor features a high sensitivity ultraviolet (UV) Parameter...
  • Page 2: Sensor Installation

    For these longer wiring runs, it may be necessary to use a pair of RG62A/U coax cables (Eclipse #21741) per scanner, with the shielding insulated and not grounded. Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016...
  • Page 3: Test Procedures

    Minimum Pilot Test Run this test on pilot ignited burners to ensure that the sensor will not detect a pilot flame too small to reliably light the main flame. Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016...
  • Page 4 2. Start the system normally. Observe the flame signal during ignition to see if it responds during the spark. Readings above 2 VDC indicate spark interference or spark sighting. 3. On pilot ignited burners, manually shut off the fuel Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016...
  • Page 5: Pilot Flame Failure Test

    4 seconds after visually observing that the flame extinguished. Limit & Interlock Tests Periodically check all interlock and limit switches by manually tripping them during burner operation to make Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016...
  • Page 6: Maintenance

    The presence of foreign material will measurably reduce the flame signal strength. Rotation To ensure operability of stored items and to reduce the possibility of extended down-time, periodically swap spare sensors and control units with active ones. Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016...
  • Page 7 2.50 Bushing (63.5) 0.38 (9.53) MIN 1/2-14 Full Threads Thread Metal 3.81 Conduit Ø1.13 0.75 1/2-14 (97.0) (28.6) 2.95 (19.0) NPSL Thread 104.5 (75.0) (2654.3) 0.47 (11.9) 15.5 (393.7) 3.20 (81.5) Eclipse 90° UV Scanner, V2, Instruction Manual 852, 5/26/2016...
  • Page 8 44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวี ว ั ฒ นา กทม. 10170. website: https://www.add-furnace.com/ e-mail: sales@add-furnace.com add028883472@gmail.com โทร.(ออกแบบ): 08-08-170-170, 088-300-1122 โทร: 02-888-3472 Online Support: Line ID: @add11 Wechat ID: add0883001122 แฟกซ์ : 02-888-3258 @add11 line ID: Eclipse 90° UV Scanner, V2, Instruction Manual 852,...

This manual is also suitable for:

Eclipse 5600-90a

Table of Contents