Access Controller - Encrypted Relay
ZIOSECV3
FEATURES
•
Actuator for one (1x) electric strike through a monostable relay
•
Encrypted communication with the access control device during the
opening of the door, either via serial communication or through a
secure KNX object (depending on the access control device)
•
Supports KNX Data Security
•
Manual output operation with push button and LED status indicator
•
Auxiliary power supply required
•
Total data saving on power failure
•
Integrated KNX BCU (TP1-256)
•
Dimensions 67 x 90 x 36 mm (2 DIN units)
•
DIN rail mounting (IEC 60715 TH35), with fixing clamp
•
Conformity with CE, UKCA, RCM directives (marks on the right side)
1. Pairing button
2. Pairing LED
7. Output control button
PROGRAMMING/TEST BUTTON: short button press to set programming mode. If this button is held while connecting the device to the auxiliary power
supply, it enters the safe mode. If this button is held for more than 3 seconds, the device enters the test mode.
PROGRAMMING/TEST LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The manual
mode is indicated by the green color. During the start-up (after reset or power failure) and if the device is not in safe mode, it emits a red flash.
PAIRING BUTTON: holding this button for more than three seconds will activate the pairing mode and delete the previous one in case the device was
paired before.
PAIRING LED: the LED will flash in blue colour while the device is unpaired. Once paired, the LED remains off.
GENERAL SPECIFICATIONS
CONCEPT
Type of device
Voltage (typical)
Voltage range
KNX supply
Maximum
consumption
Connection type
External power supply
Operation temperature
Storage temperature
Operation humidity
Storage humidity
Complementary characteristics
Protection class
Operation type
Device action type
Electrical stress period
Degree of protection
Installation
Minimum clearances
Response on external power supply failure
Response on external power supply restart
Operation indicator
Weight
PCB CTI index
Housing material
¹ Maximum consumption in the worst-case scenario (KNX Fan-In model).
© Zennio Avance y Tecnología S.L.
3. Auxiliary power
supply
8. Programming/Test button
Voltage
29 VDC (typical)
24 VDC¹
Edition 2
4. Electric strike
output
9. Programming/Test LED
DESCRIPTION
Electric operation control device
29 VDC SELV
21-31 VDC
mA
2.8
10
Typical TP1 bus connector for 0.8 mm Ø rigid cable
24 VDC. Maximum consumption: 13 mA
0 .. +55 °C
-20 .. +55 °C
5 .. 95%
5 .. 95%
Class B
III
Continuous operation
Type 1
Long
IP20, clean environment
Independent device to be mounted inside electrical panels with DIN rail (IEC
60715)
Not required
Data saving according to parameterization
Data recovery according to parameterization
The programming LED indicates programming mode (red) and test mode
(green). The output LED indicates its status (green). The pairing LED will
flash in blue while the device is unpaired.
79 g
175 V
PC FR V0 halogen free
Further information
Securel v3
TECHNICAL DOCUMENTATION
4
3
2
1
Figure 1: Securel v3
5. Encrypted communication
10. KNX connector
mW
81.2
240
www.zennio.com
5
6
7
8
9
10
11
6. Output status
LED
11. Fixing clamp
Page 1/2